11.11 o: Keypad-Related Settings
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
789
Deletes all of the saved user parameter setting values.
Set
o2-03 = 2
then push
to clear the user parameter setting values. The drive will automatically reset
o2-03
to
0
. If you delete the user parameter setting values, you cannot set
A1-03 = 1110
to initialize parameters.
■
o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name
Description
Default
(Range)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
NOTICE:
Set o2-04 [Drive Model (KVA) Selection] correctly. If you set this parameter incorrectly, it will decrease drive
performance, cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of
o2-04
changes, related parameter setting values also change. Refer to
Parameters Changed by o2-04 [Drive
Model (KVA) Selection] on page 557
for more information.
These tables list the relation between
o2-04
setting values and drive models.
■
o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name
Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push
to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
and
on
the keypad to change the frequency reference value.
■
o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name
Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
0
(0, 1)
This parameter operates even when the keypad installed to the drive becomes disconnected. This parameter is
enabled in the following circumstances.
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
•
Using Local mode
0 : Disabled
The drive continues to operate even when a keypad disconnection is detected.
1 : Enabled
Once a keypad disconnection is detected, the drive stops operating and the
oPr [Keypad Connection Fault]
indicator appears. The motor coasts to stop.
■
o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name
Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0
(0, 1)
This parameter is enabled in these conditions:
•
When
b1-02 = 0 [Run Command Selection 1 = Keypad]
or
b1-16 = 0 [Run Command Selection 2 = Keypad]
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...