YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
707
■
H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example,
set
H2-26 = 103
to monitor
U1-03 [Output Current]
.
103
(000 - 999)
Note:
•
The configurable monitor changes when the control method changes.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can set the terminal output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
•
For information on the comparator function, refer to
and
■
H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in
H2-26 [Comparator 2 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to
and
■
H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
Refer to
H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2]
for more information on
the comparator function.
■
H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
Refer to
H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2]
for more information on
the comparator function.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...