716
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■
E: Fault
Setting Value
Function
Description
E
Fault
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for
CPF00
and
CPF01 [Control Circuit Error]
faults.
■
F: Not Used
Setting Value
Function
Description
F
Not Used
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure signals from the PLC.
■
10: Alarm
Setting Value
Function
Description
10
Alarm
The terminal activates when the drive detects a minor fault.
■
11: Fault Reset Command Active
Setting Value
Function
Description
11
Fault Reset Command
Active
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or
the communication option.
■
13: Speed Agree 2
Setting Value
Function
Description
13
Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ±
L4-04 [Speed Agree Detection
Width(+/-)]
.
Note:
When using Closed Loop Vector Control, the motor speed is used as the reference.
ON : The output frequency is within the range of “frequency reference
±
L4-04
”.
OFF : The output frequency is not within the range of “frequency reference
±
L4-04
”.
■
14: User-Set Speed Agree 2
Setting Value
Function
Description
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04 [Speed
Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
Note:
•
The detection level set with
L4-03
is a signed value. Detections only occur one specific orientation.
•
When using CLV control, the motor speed is used as the reference.
ON : The output frequency is within the range of “
L4-03
±
L4-04
” and the range of the frequency
reference
±
L4-04
.
OFF : The output frequency is not within the range of “
L4-03
±
L4-04
” or the range of frequency
reference
±
L4-04
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...