YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
715
■
7: DC Bus Undervoltage
Setting Value
Function
Description
7
DC Bus Undervoltage
The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in
L2-05 [Undervoltage
Detection Lvl (Uv1)]
or less. The terminal also activates when there is a fault with the DC bus voltage.
ON : The DC bus voltage
≤
L2-05
OFF : The DC bus voltage >
L2-05
■
8: During Baseblock (N.O.)
Setting Value
Function
Description
8
During Baseblock (N.O.)
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
■
9: Frequency Reference from Keypad
Setting Value
Function
Description
9
Frequency Reference from
Keypad
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF :
b1-01 or b1-15 [Frequency Reference Selection 1 or 2]
is the frequency reference source.
■
A: Run Command from Keypad
Setting Value
Function
Description
A
Run Command Source
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF :
b1-02
or
b1-16
[Run Command Selection 1 or 2] is the Run command source.
■
B: Torque Detection 1 (N.O.)
Setting Value
Function
Description
B
Torque Detection 1 (N.O.)
The terminal activates when the drive detects overtorque.
ON : The output current/torque exceeds the torque value set with
S6-02 [Overtorque Detection
Level 1]
and remained in this state longer than the time set with
S6-03 [Overtorque Detection
Time 1]
.
Note:
Refer to
Overtorque Detection on page 214
for details.
■
C: Frequency Reference Loss
Setting Value
Function
Description
C
Frequency Reference Loss
The terminal activates when the drive detects a loss of frequency reference.
Note:
Refer to
“
L4-05: Fref Loss Detection Selection
”
for more information.
■
D: Braking Resistor Fault
Setting Value
Function
Description
D
Braking Resistor Fault
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...