INSTRUCTIONS

 

 

Copyright © SANHUA 2022

   

 

 

1

 

 

 

II-VSD2001-MU-R2206

 

Subject to change without notice

 

VSD2001 EEV Driver  

(one-driven-two)

 

 

 

 

 

SAFETY ATTENTION

 

 

 

 

1. Do not turn on the power before completing the wiring, cut off the power before changing the wiring. 

2. Although the electronic circuit inside this product has been protected to a certain extent, long-term operation 
in  a  humid  environment  will  still  cause  damage  to  components,  so  please  avoid  install  and  operate  in 
environments such as rain, moisture and with other liquids. 

3. An output wire to be used for this product should be inflammable grade FV1 (v-1 grade or above). 

4. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact 
exist. 

5. Please avoid using the product near a device generating strong high frequency noise (high frequency welding 
machine, high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR controller) 

6. Please confirm that the jumper caps and valve type parameters of the VSD2001 driver are set correctly, and 
there is no error state which green and yellow lights flashing at the same time for EEV1 and EEV2 before use. 

 

 

Summary of Contents for VSD2001 Series

Page 1: ... as rain moisture and with other liquids 3 An output wire to be used for this product should be inflammable grade FV1 v 1 grade or above 4 Please avoid installing the product in a place where a strong magnetism noise severe vibration and impact exist 5 Please avoid using the product near a device generating strong high frequency noise high frequency welding machine high frequency sewing machine hi...

Page 2: ...2 2 5 II VSD2001 EN R2206 Subject to change without notice 1 Dimensions 2 Installation Slide rail mounting Mounting VSD2001 to DIN35 slide rail through the buckle on shell Please install in a control cabinet to avoid moisture and dust ...

Page 3: ...uckles DIP SW and jumpers are on the internal PCB please follow below steps to open the shell Step 1 Squeezes the larger buckle on the side and lift the upper panel up until buckle separated 2 Step 2 Repeat step 1 on smaller buckle pull out the connected XHP terminal The upper and below panels are separated 3 Step 3 DIP switches and jumpers are located on the PCB board 1 ...

Page 4: ...e set at the same time P5 P6 P2 P3 P1 P4 Valve selection add 40105 40125 EEV1 EEV2 Description 40105 40125 address 0 0 EBV13 3500 pulse 1 1 VPF 2700 pulse 2 2 VPF 3500 pulse 3 3 VPF 3800 pulse 4 4 DPF LPF 500 pulse 5 5 EBV05 07 2800 pulse 6 6 DPF O series 2000 pulse 7 7 EBV09 3500 pulse 8 8 Customize EEV Customize detail When add 40105 8 40125 8 NO EEV1 EEV2 Function Description 1 40106 40126 Driv...

Page 5: ...se form a switch with GND 24 Power 24V 24VAC or 24VDC OPN Force open form a switch with GND 24 Power 24V GND Analog ground Connect with OPN and CLS Note 1 Cable wire range 28 12 AWG 0 2 0 8 mm 2 Do not tun on the power before completing the wiring cut off the power before changing the wiring 3 Pay attention to not reverse the EEV connection EEV1 with the analog signal 1 and the EEV 1 parameters 4 ...

Reviews: