background image

......

 Instruction Manual

SIEI

Drive

I/O expansion card

EXP-D20A6

12 Digital Inputs

8 Digital Outputs

2 Analog Inputs

2 Analog Outputs (V)

2 Analog Outputs (I)

Summary of Contents for EXP-D20A6

Page 1: ... Instruction Manual SIEI Drive I O expansion card EXP D20A6 12 Digital Inputs 8 Digital Outputs 2 Analog Inputs 2 Analog Outputs V 2 Analog Outputs I ...

Page 2: ...rvono unicamente alla descrizione del prodotto e non devono essere intesi come proprietà assicurate nel senso legale Tutti i diritti riservati Thank you for choosing this Gefran product We will be glad to receive any possible information which could help us improving this manual The e mail address is the following techdoc gefran com Keep the manual in a safe place and available to engineering and ...

Page 3: ...g Outputs Terminal Board Points 8 3 5 Schema a Blocchi Interno Functional Overview 9 4 Jumpers 10 5 LEDs 10 6 Caratteristiche Tecniche Technical Data 11 Dimensioni e peso Dimensions and weight 11 Caratteristiche generali 12 Ingressi digitali 12 Uscite digitali 12 Ingressi analogici 12 Uscite analogiche in tensione 13 Uscite analogiche in corrente 13 Temperatura 13 General data 13 Digital inputs 13...

Page 4: ...e analogiche 10V 2 uscite analogiche 20mA o 4 20mA The EXP D20A6 card is an AVy drive option used to add digital inputs digital outputs analog inputs analog outputs to the drive It is possible to use only one I O expansion card per Drive This option card features 12optocoupled digital inputs 15V up to 30VDC 8 optocoupled digital outputs 15V up to 30VDC 2 analog inputs 10V or 0 up to20mA or 4 up to...

Page 5: ... connettore XH Su questo connettore sono presenti le alimentazioni e i segnali 4 Accendere l azionamento The EXP D20A6 card is supplied with standoffs and the cable for connection between regulation and expansion card 1 Switch the drive off 2 Fasten the EXP D20A6 card to the drive regulation board by means of screws B and standoffs A 3 The EXP D20A6 card is connected to the regulator card through ...

Page 6: ... EXP D20A6 6 ...

Page 7: ... a GND Function Fw 2 X DI8X DI9X DI10X DI11X GND n a not available expDA10 XDI1 XDI0 XDI0 DIGITAL INPUTS 3 2 Connessione Uscite Digitali Digital Outputs Terminal Board Points Le uscite digitali richiedono un alimentazione esterna di 15V 24V Può essere utilizzata a tale scopo la tensione 24V disponibile in morsettiera del drive La massima caricabilità disponibile dal drive a 24V 120 mA inclusa l al...

Page 8: ...ngressi analogici sono differenziali Differential analog inputs are available Connector Terminal 1 2 3 4 5 Function Fw 1 X n a n a n a n a GND Function Fw 2 X An inp 1X An inp 1X An inp 2X An inp 2X GND n a not available expD30 ANALOG INPUTS XAI 3 4 Connessione Uscite Analogiche Analog Outputs Terminal Board Points Connector Terminal 11 12 13 14 15 Function Fw 1 X Analog output 3 GND Analog output...

Page 9: ... 58 59 31 32 33 34 DIGITAL INPUTS CONNECTOR XDIO 35 GND 36 37 38 39 DIGITAL INPUTS CONNECTOR XDI1 40 DI4X DI5X DI6X DI7X GND DI8X DI9X DI10X DI11X GND DO6X DO7X Anal out 3 An out 1X Anal out 4 An out 2X An out 3X An out 3X An out 4X An out 4X An inp 1X An inp 1X An inp 2X An inp 2X Digital input 5 DI0X Digital input DI1X 6 7 Digital input DI2X Digital input DI3X 8 Digital output 3 DO0X Digital out...

Page 10: ...enti dalla versione firmware del drive I O available depending on drive firmware version Drive firmware 1 X from 2 X Digital Inputs 4 12 Digital Outputs 6 8 Analog Inputs 2 Analog Outputs 2 4 expDA75 5 LEDs 5V Il led è acceso quando è presente la tensione 5V fornita dal Drive The led is lit when internal 5V power supply is available from the Drive 15V Il led è acceso quando il Drive fornisce la te...

Page 11: ...1 I O Expansion card 6 Caratteristiche Tecniche Technical Data Dimensioni e peso Dimensions and weight 142 49 92 36 Dimensioni Dimensions 142 49mm 5 6 inches x 92 36 mm 3 63 inches Peso Weight 77g 2 7oz ...

Page 12: ...stato alto sui pin UHigh 10V Limiti tensioni ingressi standard stato basso sui pin ULow 3V Uscite digitali Tipo uscita open emitter optoisolato Pull down 10 kΩ Numero uscite 8 Collegamento alimentazione esterna co mune Tensione di alimentazione esterna 15 30V DC Corrente di uscita 50mA max per ogni uscita Tensione di uscita UHigh Tensione di alimentazione 1V 50mA Ingressi analogici Tipo ingresso i...

Page 13: ...ionamento 0 55 C 32 131 F Queste temperature sono adeguate a quelle dell inverter a cui è collegata la scheda General data I O scan time 2ms Internal power supply from the drive 5VDC 18VDC Note The Drive TB can be used to supply 24VDC power AVy 24VDC supply maximum output 120 mA total including Encoder LAN EXP card and APC or 350 mA without APC Digital inputs Input type Voltage Optocoupled Inputs ...

Page 14: ...2 Connection differential Input voltage with Voltage ref in input 10V Current requirements with Voltage ref in input 0 5mA Input current with current ref in input 0 up to 20mA 4 up to 20mA Input impedence with current ref in input 510Ω Bandwidth 100Hz Voltage Analog outputs Output type Voltage Outputs no 2 Max Output voltage 10V Output current 5mA max Bandwidth 265Hz Current Analog outputs Output ...

Page 15: ...NIX CONTACT 5 contatti MC1 5 5 ST3 81 1803604 o equivalente Morsettiera XDQ Tipo PHOENIX CONTACT 10 contatti MC 1 5 10 ST3 81 1803659 o equivalente Terminals XDI0 XDI1 XDI2 XAI XAQV XAQI Type PHOENIX CONTACT 5 contacts MC1 5 5 ST3 81 1803604 or equivalent Terminals XDQ Type PHOENIX CONTACT 10 contacts MC 1 5 10 ST3 81 1803659 or equivalent 8 Sezione massima cavi Maximum wire sizes Terminals on con...

Page 16: ... 781 7295249 Fax 1 781 7291468 info gefraninc com GEFRAN SIEI ASIA Blk 30 Loyang way 03 19 Loyang Industrial Estate 508769 SINGAPORE Ph 65 6 8418300 Fax 65 6 7428300 info gefransiei com sg GEFRAN INDIA Pvt Ltd Head office Pune office Survey No 182 1 KH Bhukum Paud road Taluka Mulshi Pune 411 042 MH INDIA Ph 91 20 3939 4400 Fax 91 20 3939 4401 gefran india gefran in Branch office Mumbai office Laxm...