List of messages
ID
Level
Message
Description
1800
Info
On module <%s1>, the temperature <%s2> exceeded the normal
level.
Meaning: The temperature at the part shown in %s2 of the module shown in %s1 is beyond
the normal value but does not reach the warning level.
Action: Nothing required. If this message frequently appears, check if something prevents the
unit from cooling down
1801
WARNING
On module <%s1>, the temperature <%s2> exceeded the warning
level.
Meaning: The temperature at the part shown in %s2 of the module shown in %s1 is beyond
the warning level.
Action: Although the device can keep running, the high temperature can cause a fault. Thus,
check if something prevents it from cooling down, such as failure in air conditioners or in fan
modules of the unit, and inlet ports covered with dust.
1802
FAIL
On module <%s1>, the temperature <%s2> rose too far above
tolerable levels.
Meaning: The temperature at the part shown in %s2 of the module shown in %s1 is
exceedingly high.
Action: The module with a high temperature may stop working to protect hardware. Consult
your reseller or maintenance personnel.
Check if something prevents it from cooling down, such as failure in air conditioners or in fan
modules of the unit, and inlet ports covered with dust.
1803
WARNING
On module <%s1>, the temperature <%s2> fell below the warning
level.
Meaning: The temperature at the part shown in %s2 of the module shown in %s1 is below the
warning level.
Action: Although the device can keep working, check if the temperature is proper where the
device is installed.
1805
Info
On module <%s1>, the temperature <%s2> has been restored to a
tolerable level.
Meaning: The temperature at the part shown in %s2 of the module shown in %s1 is back to
the normal level.
Action: This shows just information. Nothing required.
1810
WARNING
On module <%s1>, the voltage <%s2> exceeded the warning level.
Meaning: The voltage at the part shown in %s2 of the module shown in %s1 is beyond the
warning level.
Action: Although the device can keep working, the high voltage can cause a fault. Consult
your reseller or maintenance personnel.
1811
FAIL
On module <%s1>, the voltage <%s2> rose too far above tolerable
levels.
Meaning: The voltage at the part shown in %s2 of the module shown in %s1 is exceedingly
high.
Action: The module with high voltage may stop working to protect hardware. Consult your
reseller or maintenance personnel.
1813
WARNING
On module <%s1>, the voltage <%s2> fell below the warning level.
Meaning: The voltage at the part shown in %s2 of the module shown in %s1 is below the
warning level.
Action: Although the device can keep working, the low voltage can cause a fault. Consult
your reseller or maintenance personnel.
1814
FAIL
On module <%s1>, the voltage <%s2> fell too far below tolerable
Содержание Compute Blade 2000
Страница 1: ...MK 99BDS2K001 16 Hitachi Compute Blade 2000 User s Guide ...
Страница 42: ...xlii Precautions for Safe Use Rear View of A1 A2 Chassis ...
Страница 43: ...xliii Precautions for Safe Use Rear View of A2 Chassis ...
Страница 44: ...xliv Precautions for Safe Use Server Blade ...
Страница 45: ...xlv Precautions for Safe Use I O Slot Expansion Unit ...
Страница 46: ...xlvi Precautions for Safe Use I O Module ...
Страница 47: ...xlvii Precautions for Safe Use AC Power Input Module ...
Страница 51: ...li How to Use the Manuals This page is intentionally left blank ...
Страница 61: ...10 1 Before Use ...
Страница 64: ...13 2 How to Use the System Equipment Rear view of A1 chassis Rear view of A2 chassis ...
Страница 93: ...42 2 How to Use the System Equipment ...
Страница 123: ...72 3 Connecting the System Equipment and Powering On ...
Страница 252: ...201 5 Server Blade Setup 7 Click Next The following screen appears 8 Click Add to SPAN The following screen appears ...
Страница 266: ...215 5 Server Blade Setup 12 Click Yes The following screen appears 13 Click Next The following screen appears ...
Страница 272: ...221 5 Server Blade Setup 3 Check Del and click Go The following screen appears 4 Click Yes ...
Страница 277: ...226 5 Server Blade Setup 3 Check Make Global HSP 4 Click Go Hotspare is set to the specified hard disk ...
Страница 332: ...281 5 Server Blade Setup 7 Click Next The following screen appears 8 Click Add to SPAN The following screen appears ...
Страница 345: ...294 5 Server Blade Setup 12 Click Next The following screen appears ...
Страница 351: ...300 5 Server Blade Setup 3 Check Delete and click Go The following screen appears 4 Click Yes ...
Страница 368: ...317 5 Server Blade Setup 5 Confirm that Controller BIOS is set to that value 6 Click Home to return to the main menu ...
Страница 426: ...375 5 Server Blade Setup 3 Check Delete and click Go The following screen appears 4 Click Yes ...
Страница 430: ...379 5 Server Blade Setup 3 Click Go Hotspare is set to the specified hard disk ...
Страница 473: ...422 5 Server Blade Setup iSCSI menu On the iSCSI menu you can check iSCSI settings Figure 5 42 iSCSI selection menu ...
Страница 479: ...428 5 Server Blade Setup ...
Страница 717: ...666 6 Management Module Settings Details of a physical partition ...
Страница 722: ...671 6 Management Module Settings Server blade details view ...
Страница 723: ...672 6 Management Module Settings ...
Страница 732: ...681 6 Management Module Settings Management module details view ...
Страница 745: ...694 6 Management Module Settings Optional Physical WWN list view ...
Страница 748: ...697 6 Management Module Settings Optional Physical WWN initialization view ...
Страница 750: ...699 6 Management Module Settings FRU list view Displays FRU information for all installed modules ...
Страница 751: ...700 6 Management Module Settings ...
Страница 752: ...701 6 Management Module Settings Sensor list view Displays sensor information for all installed modules ...
Страница 754: ...703 6 Management Module Settings Power status details view ...
Страница 767: ...716 6 Management Module Settings ...
Страница 768: ...717 6 Management Module Settings ...
Страница 769: ...718 6 Management Module Settings ...
Страница 814: ...763 6 Management Module Settings Power status trend view partition ...
Страница 817: ...766 6 Management Module Settings Access log display view ...
Страница 819: ...768 6 Management Module Settings WWN change log display view ...
Страница 879: ...828 7 Configuring the LAN Switch Module Link aggregation adding editing screen ...
Страница 899: ...848 8 Configuring the 10 Gb DCB Switch Module ...
Страница 919: ...868 10 Configuring the Fibre Channel Switch Module ...
Страница 931: ...880 11 I O Slot Expansion Unit Account setting You can use the console to set accounts For procedures see SO command ...
Страница 1097: ...1046 12 Logical partitioning manager Click Confirm and the OS setting is updated as shown in the following screen ...
Страница 1535: ...1484 12 Logical partitioning manager ...
Страница 1877: ...1826 14 14 When You Need Help ...
Страница 1925: ...16 Glossary ...
Страница 1926: ...Hitachi Compute Blade 2000 User s Guide ...