14-160
IM 05P07A01-01EN
14.6 GREEN Series Compatible D Registers
Loop-1 Alarm-1 setpoint to Alarm-8 setpoint of Groups 3
When D0917 (AL3.1) = 4, 6, 14, 16
Symbol
Event
GREEN Series
UTAdvanced
D0304
1.A3
A3_L1_1 (D2506)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A3=10 → 1.A3=-10)
D0329
2.A3
A3_L1_2 (D2526)
D0354
3.A3
A3_L1_3 (D2546)
D0379
4.A3
A3_L1_4 (D2566)
D0404
5.A3
A3_L1_5 (D2586)
D0429
6.A3
A3_L1_6 (D2606)
D0454
7.A3
A3_L1_7 (D2626)
D0479
8.A3
A3_L1_8 (D2646)
Loop-1 Alarm-1 setpoint to Alarm-8 setpoint of Groups 4
When D0918 (AL4.1) = 4, 6, 14
Symbol
Event
GREEN Series
UTAdvanced
D0305
1.A4
A4_L1_1 (D2507)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A4=10 → 1.A4=-10)
D0330
2.A4
A4_L1_2 (D2527)
D0355
3.A4
A4_L1_3 (D2547)
D0380
4.A4
A4_L1_4 (D2567)
D0405
5.A4
A4_L1_5 (D2587)
D0430
6.A4
A4_L1_6 (D2607)
D0455
7.A4
A4_L1_7 (D2627)
D0480
8.A4
A4_L1_8 (D2647)
D0502 to D0680: A1_L2_1 to A4_L2_8 (Loop-2 Alarm-1 setpoint to Alarm-8
setpoint of Groups 1 to 4)
When the Loop-2 Alarm-1 setpoint to Alarm-4 setpoint (D0955: AL1.2, D0956: AL2.2,
D0957: AL3.2, D0958: AL4.2) are the following values (Deviation low limit alarm), the
sign of the alarm setpoint is reversed and is set to UTAdvanced.
AL1.2, AL2.2, AL3.2, AL4.2 = 4, 6, 14, 16
(For 4 to 46, refer to "
D0302 to D0480: A1_L1_1 to A4_L1_8" in the previous section.)
(If the setting value is other than the above, the alarm setpoint is not changed.)
Loop-2 Alarm-1 setpoint to Alarm-8 setpoint of Groups 1
When D0955 (AL1.2) = 4, 6, 14, 16
Symbol
Event
GREEN Series
UTAdvanced
D0502
1.A1
A1_L2_1 (D3604)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A1=10 → 1.A1=-10)
D0527
2.A1
A1_L2_2 (D3624)
D0552
3.A1
A1_L2_3 (D3644)
D0577
4.A1
A1_L2_4 (D3664)
D0602
5.A1
A1_L2_5 (D3684)
D0627
6.A1
A1_L2_6 (D3704)
D0652
7.A1
A1_L2_7 (D3724)
D0677
8.A1
A1_L2_8 (D3744)
Loop-2 Alarm-1 setpoint to Alarm-8 setpoint of Groups 2
When D0956 (AL2.2) = 4, 6, 14, 16
Symbol
Event
GREEN Series
UTAdvanced
D0503
1.A2
A2_L2_1 (D3605)
The sign of the alarm setpoint is reversed and is set to UTAdvanced.
(Example: 1.A2=10 → 1.A2=-10)
D0528
2.A2
A2_L2_2 (D3625)
D0553
3.A2
A2_L2_3 (D3645)
D0578
4.A2
A2_L2_4 (D3665)
D0603
5.A2
A2_L2_5 (D3685)
D0628
6.A2
A2_L2_6 (D3705)
D0653
7.A2
A2_L2_7 (D3725)
D0678
8.A2
A2_L2_8 (D3745)