2-5
IM 05P07A01-01EN
Setting Communication Functions
2
2.1.3 Setting Coordinated Operation
Parameter Setting Display
UT75A/UT55A/UT35A/UP55A/UP35A:
Operation Display >
PARAMETER
and
Left arrow
keys
simultaneously for 3 seconds (to the [
CTL
] Menu Display) >
Right
arrow
key (to the [
R485
] Menu Display in E3 or E4
*1
) >
SET/ENTER
key (The setting parameter is displayed.)
*1: Only UT75A/UT55A/UP55A. UT35A/UP35A does not have R485 of E4.
(UT75A/UT55A/UP55A: E3 or E4 indicating the terminal area is displayed
on Group display. UT35A/UP35A: E3 indicating the terminal area is
displayed on Group display.)
UT52A/UT32A/UP32A:
Operation Display >
PARA
and
Left arrow
keys simultaneously for
3 seconds (to the [
CTL
] Menu Display) >
Right arrow
key (to the
[
R485
] Menu Display in E1) >
SET/ENTER
key (The setting parameter
is displayed.) (E1 indicating the terminal area is displayed on Group
display.)
Setting Details
Parameter
Group
display
Name
Setting Range
Menu symbol Factory Default
PSL
UT75A/
UT55A/
UP55A:
E3 or E4
UT35/
UP35A:
E3
UT52A/
UT32A/
UT32A-D/
UP32A/U:
E1
Protocol
selection
Coordinated master
station
CO-M (3)
R485
PLC (0)
Coordinated slave
station
CO-S (4) *3
Coordinated master
station (2-loop mode) CO-M2 (9) *4
Coordinated slave
station (Loop-1 mode) CO-S1 (10) *3
Coordinated slave
station (Loop-2 mode) CO-S2 (11) *3
BPS
Baud rate
600 bps
600 (0)
19200 (5)
1200 bps
1200 (1)
2400 bps
2400 (2)
4800 bps
4800 (3)
9600 bps
9600 (4)
19200 bps
19200 (5)
38400 bps *1
38400 (6)
PRI
Parity
None
NONE (0)
EVEN (1)
Even
EVEN (1)
Odd
ODD (2)
STP
Stop bit
1 bit
1 (1)
1 (1)
2 bits
2 (2)
DLN
Data length
7 bits
7 (7)
8 bits (8)
8 bits
8 (8)
ADR
Address
1 to 99
1
RP.T
*2
Minimum
response time
0 to 10 (x10ms)
0
Note: Figures in parentheses "( )" are values to be set when performing communication.
*1: 38400 bps can be specified when the UT75A/UT55A/UT35A/UP55A/UP35A suffix code Type
3 = 1 or UT52A/UT32A/UT32A-D/UP32A suffix code Type 2 = 1.
*2:
This parameter may not be displayed depending on the parameter display level (LEVL) setting.
*3: UT75A/UT55A/UT52A/UT35A/UT32A/UT32A-D only.
*4: UT75A/UP55A only.
►
UTAdvanced Operation Guide or User’s Manual
Description
Master controller: UT75A/UT55A/UT52A/UT35A/UT32A/UP55A/UP35A/UP32A
Slave controller: UT75A/UT55A/UT52A/UT35A/UT32A/UT32A-D
►
Description of parameters: 2.2.1 Setting RS-485 Communication (for UTAdvanced with RS-485
communication)
2.1 Setting Parameters
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...