8-111
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Ref.
No.
H No.
Register
symbol
R/W
Description
Range and meaning of value
D8109 48109 1FAC
PV.TY1
R/W
PV event-1 type
OFF: Disable
(Energized)
1: PV high limit, 02: PV low limit,
3: SP high limit, 04: SP low limit,
5: Deviation high limit,
6: Deviation low limit,
7: Deviation high and low limits,
8: Deviation within high and low limits,
9: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low
limits,
15: OUT high limit,
16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when
the PV high limit is de-energized, the setting
is 101.
D8110 48110 1FAD
PV.EV1
R/W
PV event-1 setpoint
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, or output alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input
type.
D8111
48111 1FAE
PV.TY2
R/W
PV event-2 type
Same as D8109
D8112 48112 1FAF
PV.EV2
R/W
PV event-2 setpoint
Same as D8110
D8113 to D8124
D8125 48125 1FBC
TME1
R/W Start condition of time event 1
0: OFF (Start OFF state)
1: ON (Start ON state)
D8126 48126 1FBD
T.ON1
R/W On time of time event 1
0: Unregistered
1 to 59999 (minute or second)
* Available only within the segment time.
* OFF when the operation mode is changed to
the mode except the program operation.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
D8127 48127 1FBE
T.OF1
R/W
Off time of time event 1
D8128 48128 1FBF
TME2
R/W Start condition of time event 2
Same as D8125
D8129 48129 1FC0
T.ON2
R/W On time of time event 2
Same as D8126
D8130 48130 1FC1
T.OF2
R/W
Off time of time event 2
Same as D8127
D8131 48131 1FC2
TME3
R/W Start condition of time event 3
Same as D8125
D8132 48132 1FC3
T.ON3
R/W On time of time event 3
Same as D8126
D8133 48133 1FC4
T.OF3
R/W
Off time of time event 3
Same as D8127
D8134 48134 1FC5
TME4
R/W Start condition of time event 4
Same as D8125
D8135 48135 1FC6
T.ON4
R/W On time of time event 4
Same as D8126
D8136 48136 1FC7
T.OF4
R/W
Off time of time event 4
Same as D8127
D8137 to D8172
D8173 48173 1FEC PTN.ERR
R
Read/write error information
0: normal end
Except 0: error (See "Error information"
described later in this chapter.)
D8174 to D8200
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...