8-78
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Key Operation Setting, Display Function Setting, and SELECT Display Setting (D5701 to D5800)
Register
No.
Description
Range and meaning of value
D5701
F1
*
1
User function key-1 action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
5: S/R (STOP/RUN switch)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
9: REM1 (Switch to REM)
10: LCL1 (Switch to LCL)
13: STOP (Switch to STOP)
14: RUN (Switch to RUN)
17: AT (Auto-tuning)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
D5702
F2
*
1
User function key-2 action setting
D5703
Fn
*
1
User function key-n action setting
D5704
A/M-K
*
1
A/M key action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
5: S/R (STOP/RUN switch)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
D5705
RUN-K
*
1
RUN key action setting
0: OFF (Disable)
1: PROG (Switch to PROG (Start of program operation))
2: RESET (Switch to RESET (Stop of program operation))
3: LOCAL (Switch to LOCAL(LSP) (Start of local-mode operation))
5: P/R (PROG/RESET switch)
6: P/H (PROG/HOLD switch)
7: P/L (PROG/LOCAL(LSP) switch)
9: HLD (Switch to HOLD (Start of hold-mode operation))
10: ADV (Advance of segment)
11: A/M (AUTO/MAN switch)
13: PRG1 (Switch to PROG1 (Start of program-1 operation)
14: PRG2 (Switch to PROG2 (Start of program-2 operation)
17: AT (Auto-tuning)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
24: PTN (Program pattern number switch)
25: MODE (Operation mode)
D5706
RST-K
*
1
RST key action setting
D5707
PTN-K
*
1
PTN Key action setting
D5708
MODE-K
*
1
MODE key action setting
D5709 to D5712
D5713
PCMD_L1
Active color PV display switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF: red, Alarm ON: white)
6: P
V limit (Within range: white, Out of range: red)
7: PV limit (Within range: red, Out of range: white)
8: SP deviation (Within deviation: white, Out of
deviation: red)
9: SP deviation (Within deviation: red, Out of deviation:
white)
10: Link to DI (ON: red, OFF: white)
D5714
PCH_L1
PV color change high limit
S
et a display value when in PV limit or SP deviation.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
D5715
PCL_L1
PV color change low limit
D5716 to D5718
*1: Same parameter exists in other menu. “-K” is added to the end of the parameter in KEY
menu.