![YOKOGAWA UTAdvanced Series User Manual Download Page 375](http://html1.mh-extra.com/html/yokogawa/utadvanced-series/utadvanced-series_user-manual_3541677375.webp)
8-50
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Control Action-related Setting (D4601 to D4700)
Register
No.
Description
Range and meaning of value
D4601
SC_L2
Super function
0: OFF (Disable)
1: Overshoot suppressing function (normal mode)
2: Hunting suppressing function (stable mode)
Enables to answer the wider characteristic
changes compared with response mode.
3: Hunting suppressing function (response mode)
Enables quick follow-up and short converging
time of PV for the changed SP.
4: Overshoot suppressing function (strong
suppressing mode)
Note: Setpoints 2 and 3 must be used in PID control
or PI control. Disabled in the following controls:
1) ON/OFF control, 2) PD control, 3) P control,
4) Heating/cooling control
Do not use the function for the control
processes with response such as flow or
pressure control.
D4602
D4603
AT.TY_L2
Auto-tuning type
0: Normal
1: Stability
D4604
AT.OH_L2
Output high limit in auto-tuning
-5.0 to 105.0%
D4605
AT.OL_L2
Output low limit in auto-tuning
D4606
AT.BS_L2
SP bias in auto-tuning
-100.0 to 100.0% of PV input range span (EUS)
D4607 to D4625
D4626
A
R_L2
Anti-reset windup (excess integration
prevention)
0: AUTO, 50.0 to 200.0%
D4627
O
PR_L2
Output velocity limiter
0: OFF (Disable), 0.1 to 100.0%/s
D4628
O
LMT_L2
Output limiter switch
0: OFF (Disable output limiter in MAN mode)
1: ON (Enable output limiter in MAN mode)
D4629 to D4630
D4631
MPON_L2
Manual preset output number selection
Select the output used in MAN mode when
switched from AUTO to MAN mode.
0: OFF (Hold the control output in AUTO mode
(bumpless))
1: Use manual preset output 1 (output bump)
2: Use manual preset output 2 (output bump)
3: Use manual preset output 3 (output bump)
4: Use manual preset output 4 (output bump)
5: Use manual preset output 5 (output bump)
D4632
MPO1_L2
Manual preset output 1
-5.0 to 105.0%
However, output is limited to the output high limit
and low limit.
D4633
MPO2_L2
Manual preset output 2
D4634
MPO3_L2
Manual preset output 3
D4635
MPO4_L2
Manual preset output 4
D4636
MPO5_L2
Manual preset output 5
D4637 to D4652