8-87
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
DO Function Setting (D6201 to D6300)
Register
No.
Description
Range and meaning of value
D6201
AL1.S
AL1 function selection
Set an I relay number (Setting range: 4001 to 6000,
UP35A: 4001 to 6304).
Ex.) Set the number 4353 for AL1.S to use the alarm 1.
0: OFF (No function)
UT35A/UT32A
Alarm 1: 4353
Alarm 2: 4354
Alarm 3: 4355
Alarm 4: 4357
AUTO (ON ) / MAN (OFF) status: 4193
REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
UP35A
0: OFF (No function)
PV event-1:
4801
PV event-2
: 4802,
Time event 1: 4817,
Time event 2: 4818,
Time event 3: 4819,
Time event 4: 4821,
Alarm 1: 4353,
Alarm 2: 4354,
AUTO (ON ) / MAN (OFF) status: 4177,
Program RESET status: 4181,
Program RUN status: 4182,
Local operation status: 4183,
HOLD mode status: 4189,
Program advance status: 4187,
Pattern end signal (1 second): 4265,
Pattern end signal (3 seconds): 4266,
Pattern end signal (5 seconds): 4267,
Wait end signal (1 second) : 4257,
Wait end signal (3 seconds) : 4258,
Wait end signal (5 seconds) : 4259,
For the items other than below, see the Chapter 9
Functions and Applications of I Relays (for UT35A/UT32A/
UT32A-D/UP35A/UP32A).
D6202
AL2.S
AL2 function selection
D6203
AL3.S
AL3 function selection
D6204
OR.S
OUT relay function selection
D6205
OR2.S
OUT2 relay function selection
D6206
AL1.D
AL1 contact type
0: When the event of assigned function occurs, the
contact is closed.
1: When the event of assigned function occurs, the
contact is opened.
D6207
AL2.D
AL2 contact type
D6208
AL3.D
AL3 contact type
D6209
OR.D
OUT relay contact type
Same as D6206
D6210
OR2.D
OUT2 relay contact type
D6211 to D6220
D6221
DO1.S_E1
DO11 function selection
Same as D6201
D6222
DO2.S_E1
DO12 function selection
D6223
DO3.S_E1
DO13 function selection
D6224
DO4.S_E1
DO14 function selection
D6225
DO5.S_E1
DO15 function selection
D6226
DO1.D_E1
DO11 contact type
Same as D6206
D6227
DO2.D_E1
DO12 contact type
D6228
DO3.D_E1
DO13 contact type
D6229
DO4.D_E1
DO14 contact type
D6230
DO5.D_E1
DO15 contact type
D6231 to D6280
D6281
DO1.S_E4
DO41 function selection
Same as D6201
D6282
DO2.S_E4
DO42 function selection
D6283
DO3.S_E4
DO43 function selection
D6284
DO4.S_E4
DO44 function selection
D6285
DO5.S_E4
DO45 function selection