8-21
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Operation Mode and
Alarm Setpoint Setting for UP35A
(D2301 to D2400)
Register
No.
Description
Range and meaning of value
D2301
A.M_L1
AUTO/MAN switch
0: AUTO (Automatic mode)
1: MAN (Manual mode)
D2302
A.M_L2
Loop-2 AUTO/MAN switch
D2303
D2304
S.R_L1
STOP/RUN switch
0: RUN (Run mode)
1: STOP (Stop mode)
Preset output (PO) is generated in STOP mode.
Default: Not displayed. STOP/RUN switch is
assigned to contact input.
D2305
S.R_L2
Loop-2 STOP/RUN switch
D2306
R.L_L1
REMOTE/LOCAL switch
0: LCL (Local mode)
1: REM (Remote mode)
(Displayed only in cases where the communication
is specified.)
D2307
R.L_L2
Loop-2 REMOTE/LOCAL switch
D2308
AT_L1
Auto-tuning switch
0: OFF (Disable)
1 to 4: Perform auto-tuning. Tuning result is stored
in the specified numbered PID.
9: R (Tuning result is stored in the PID for reference
deviation.)
D2309
AT_L2
Loop-2 auto-tuning switch
D2310 to D2311
D2312
SPNO.
SP number selection
1 to 4 (Depends on the setup parameter SPGR.
setting.)
D2313
D2314
TRK_ON_L1
Output tracking status
0: OFF
1: ON
D2315
TRK_ON_L2
Loop-2 output tracking status
D2316
MODE
Operation mode
(Start/stop of program operation /
start of local-mode operation / start of
remote-mode operation)
0: RESET (Stop of program operation)
1: PROG (Start of program operation)
2: LOCAL (Start of local-mode operation)
D2317
HOLD
Pause/cancel release of program
operation
Display during program operation.
0: OFF (Cancel release (Program operation
restart))
1: ON (Pause)
D2318
ADV
Advance of segment
Display during program operation.
Set as “ADV = 1 (ON)” to advance from the current
segment to the next segment.
D2319
A.M_L1
AUTO/MAN switch
0: AUTO (Automatic mode)
1: MAN (Manual mode)
D2320 to D2321
D2322
PTNO.
Program pattern number selection
0: Not select program pattern
1 to 2 (4 when the option “/AP” is specified.)
D2323 to D2330
D2331
C.RSP_L1
Communication remote setpoint
0.0 to 100.0% of PV input range (EU)
D2332
C.RSP_L2
Loop-2 communication remote
setpoint
D2333
MOUT_L1
Heating-side control output in MAN
mode
0.0 to 105.0% (Standard type: -5.0 to 105.0%)
D2334
MOUTc_L1
Cooling-side control output in MAN
mode
0.0 to 105.0%
D2335
MOUT_L1
Heating-side control output in MAN
mode
0.0 to 105.0% (Standard type: -5.0 to 105.0%)
D2336
MOUTc_L1
Cooling-side control output in MAN
mode
0.0 to 105.0%
D2337
H.SP_L1
SP for HOLD state
0.0 to 100.0% of PV input range (EU)
D2338
D2339
H.TSP_L1
TSP for HOLD state
0.0 to 100.0% of PV input range (EU)
D2340
D2341
H.TM
HOLD time
0 to 59999 (minute or second)
* Use the parameter TMU to set the time unit.