3-40
IM 05P07A01-01EN
3.2.7 Communication with FA-M3
Host computers that can use PC link communication protocol can communicate with
FA-M3.
Communication with FA-M3 (UT link module)
The UTAdvanced can communicate with FA-M3 simply by connecting to the UT link
module by PC link communication protocol.
Set the communication conditions on the UTAdvanced to the same conditions as those
on the UT link module.
Communication with UT Link Module
FA-M3
UT link module model name: F3LC51-2N
Up to 31 connected slaves with a maximum length of 1200 m
The UT link module supports two types of communication modes and command
communication. So, data transactions are possible without being aware of
communication. For details, see the "UT Link Module User’s Manual (IM 34M06H25-
01E)."
1. AUTO (automatic) mode
In this mode, fixed devices on the controller (not user-specifiable) are read and
refreshed.
Fixed devices are D registers D2001 to D2025. Fixed devices cannot be written as
they are the read area on the UTAdvanced.
2. MAN (manual) mode
In this mode, the devices (user-specifiable) on the UTAdvanced are read/written and
refreshed manually.
► "Devices" here refers to D registers and I relays.
D registers and I relays: Chapter 6 Functions and Applications of D Registers (for UT55A/
UT52A/UP55A) or Chapter 7 Functions and Application of I Relays (for UT55A/UT52A/UP55A)
D registers and I relays: Chapter 8 Functions and Applications of D Registers (for UT35A/
UT32A/UT32A-D/UP35A/UP32A) or Chapter 9 Functions and Application of I Relays (for
UT35A/UT32A/UT32A-D/UP35A/UP32A)
D registers and I relays: Chapter 10 Functions and Applications of D Registers (for UM33A) or
Chapter 11 Functions and Application of I Relays (for UM33A)
D registers and I relays: Chapter 12 Functions and Applications of D Registers (for UT35A-L) or
Chapter 13 Functions and Application of I Relays (for UT35A-L)
D registers and I relays: Chapter 14 Functions and Applications of D Registers (for UT75A) or
Chapter 15 Functions and Application of I Relays (for UT75A)
3. Command operation
In this mode, the devices can be accessed whenever necessary.
3.2 PC Link Communication
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...