Functions and
Applications of D Registers (for UT75A)
14
14.5 Writing via Communication
Setting Target Setpoint
In LCL (local) mode
(1) Set the Loop-1 and Loop-2 target setpoints of groups 1 to 8 parameters (SP_L1_1
to SP_L1_8 or SP_L2_1 to SP_L2_8).
(2) Write the setpoint (1 to 8) in the SPNO. (SP number selection) (depends on the
setup parameter SPGR. setting)
(3) Set the operation mode (R.L_L1, R.L_L2) to LCL (local) (0).
Register No. Register symbol
Description
D2312
SPNO.
SP number selection
In REM (remote) mode
(1) The target setpoint can be written via communication only when the operation
mode (R.L_L1, R.L_L2) is set to REM (remote) mode.
(2) Write the setpoint in the C.RSP_L1 or C.RSP_L2.
Example: When setting 150.0
°
C for the C.RSP_L1, write
“1500” to this register.
(3) Set the operation mode (R.L_L1, R.L_L2) to the REM (remote) mode.
Register No. Register symbol
Description
D2331
C.RSP_L1
Loop-1 communication remote setpoint
D2332
C.RSP_L2
Loop-2 communication remote setpoint
Setting Control Output Value in MAN Mode
The control output value can be written via communication only when the operation
mode is set to MAN mode.
(1) Set the operation mode (A.M) to MAN (1).
(2) Write the control output value in the MOUT_L1, MOUT_L2, MOUTc_L1, or
MOUTc_L2.
Register No. Register symbol
Description
D2333
MOUT_L1
Loop-1 heating-side control output in MAN mode
D2334
MOUTc_L1
Loop-1 cooling-side control output in MAN mode
D2335
MOUT_L2
Loop-2 heating-side control output in MAN mode
D2336
MOUTc_L2
Loop-2 cooling-side control output in MAN mode
Setting Manual Preset Output Number
The manual preset output number can be written via communication only when the
operation mode is set to MAN mode.
(1) Set the Loop-1 and Loop-2 manual preset output 1 to 5 parameters (MPO1_L1 to
MPO5_L1 or MPO1_L2 to MPO5_L2).
(2) Write the setpoint (1 to 5) in the MPON_L1 or MPON_L2.
(3) Set the operation mode (A.M) to MAN (1).
Register No. Register symbol
Description
D3531
MPON_L1
Loop-1 manual preset output number selection
D4631
MPON_L2
Loop-2 manual preset output number selection
Operating a Valve (for Position proportional type only)
Write a valve position in MOUT_L1 in MAN mode for position proportional PID
computation.