10-36
IM 05P07A01-01EN
10.4 UM33A D Registers
Key Operation Setting, Display Function Setting, and SELECT Display Setting (D5701 to D5800)
Register
No.
Description
Range and meaning of value
D5701 to D5702
D5703
Fn
*
1
User function key-n action setting
0: OFF (Disable)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
24: AL (Alarm Setpoint Setting)
25: RST (PV peak and bottom values reset)
D5704 to D5712
D5713
PCMD_L1
Active color PV display switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF: red, Alarm ON: white)
6: P
V limit (Within range: white, Out of range: red)
7: PV limit (Within range: red, Out of range: white)
10: Link to DI (ON: red, OFF: white)
D5714
PCH_L1
PV color change high limit
S
et a display value when in PV limit or SP deviation.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
D5715
PCL_L1
PV color change low limit
D5716 to D5722
D5723
EV1_L1
EV1 display condition registration
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4326: Link to alarm 5 (Lit when the alarm occurs)
4327: Link to alarm 6 (Lit when the alarm occurs)
4329: Link to alarm 7 (Lit when the alarm occurs)
4330: Link to alarm 8 (Lit when the alarm occurs)
5025 to 5026: Link to DI1-DI2 (Lit when the contact is
closed)
5153 to 5155: Link to AL1-AL3 (Lit when the contact is
closed)
5156: Link to AL4 (Lit when the contact is closed)
5169 to 5173: Link to DO11-DO15 (E1- terminal area)
(Lit when the contact is closed)
For other functions, see the Chapter 11 Functions and
Applications of I Relays (for UM33A).
*: Initial value. The contact action changes by the
setting of each "contact type" parameter.
D5724
EV2_L1
EV2 display condition registration
D5725
EV3_L1
EV3 display condition registration
D5726
EV4_L1
EV4 display condition registration
D5727 to D5738
D5739
PV.D
PV display area ON/OFF
0: OFF (Nondisplay)
1: ON (Display)
D5740
SP.D
Setpoint display area ON/OFF
D5741
STS.D
Status display area ON/OFF
D5742
SPD
Scroll speed
(Slow) 1 to 8 (Quick)
D5743
GUID
Guide display ON/OFF
0: OFF (Nondisplay)
1: ON (Display)
*1: Same parameter exists in other menu. “-K” is added to the end of the parameter in KEY
menu.