6-95
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Key Operation Setting, Display Function Setting, and SELECT Display Setting (D5701 to D5800)
Register
No.
Description
Range and meaning of value
D5701
F1
*
1
User function key-1 action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
2: C/A/M (CAS/AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
4: R/L2 (Loop-2 REM/LCL switch)
5: S/R (STOP/RUN switch)
6: CAS (Switch to CAS)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
9: REM1 (Switch to REM)
10: LCL1 (Switch to LCL)
11: REM2 (Switch to Loop-2 REM)
12: LCL2 (Switch to Loop-2 LCL)
13: STOP (Switch to STOP)
14: RUN (Switch to RUN)
17: AT (Auto-tuning)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
Loop-2 setting values are unavalable in Single-loop control.
D5702
F2
*
1
User function key-2 action setting
D5703
Fn
*
1
User function key-n action setting
D5704
A/M-K
*
1
A/M key action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
2: C/A/M (CAS/AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
4: R/L2 (Loop-2 REM/LCL switch)
5: S/R (STOP/RUN switch)
6: CAS (Switch to CAS)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
D5705
RUN-K
*
1
RUN key action setting
0: OFF (Disable)
1: PROG (Switch to PROG (Start of program operation))
2: RESET (Switch to RESET (Stop of program operation))
3: LOCAL (Switch to LOCAL(LSP) (Start of local-mode operation))
4: REM (Switch to REMOTE)
5: P/R (PROG/RESET switch)
6: P/H (PROG/HOLD switch)
7: P/L (PROG/LOCAL(LSP) switch)
8: L/C (LOCAL(LSP)/CAS switch)
9: HLD (Switch to HOLD (Start of hold-mode operation))
10: ADV (Advance of segment)
11: A/M1 (AUTO/MAN switch)
12: A/M2 (Loop-2 AUTO/MAN switch)
13: PRG1 (Switch to PROG1 (Start of program-1 operation)
14: PRG2 (Switch to PROG2 (Start of program-2 operation)
17: AT (Auto-tuning)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
24: PTN (Program pattern number switch)
25: MODE (Operation mode)
D5706
RST-K
*
1
RST key action setting
D5707
PTN-K
*
1
PTN Key action setting
D5708
MODE-K
*
1
MODE key action setting
D5709 to D5710
D5711
DVB_L1
Loop-1 deviation display band
Permits a change in the span of deviation shown on
the front-panel deviation monitor.
Displayed only for UT55A.
0.0 to 100.0% of PV input range span (EUS)
D5712
D
VB_L2
Loop-2 deviation display band
*1: Same parameter exists in other menu. “-K” is added to the end of the parameter in KEY
menu.
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...