6-14
IM 05P07A01-01EN
6.4 UT55A/UT52A/UP55A D Registers
Bit Configuration of D2039: PV_EV (PV event status)
Bit
Symbol
Event
0
PV_EV1
0: PV eve
nt is OFF
1: PV event is ON
1
PV_EV2
2
PV_EV3
3
4
PV_EV4
0: PV event is OFF
1: PV event is ON
5
PV_EV5
6
PV_EV6
7
8
PV_EV7
0: PV event is OFF
1: PV event is ON
9
PV_EV8
10 to 15
Bit Configuration of D2040: TIME_EV_1 (Time event status 1)
Bit
Symbol
Event
0
TIME_EV1
0: Time event is OFF
1: Time event is ON
1
TIME_EV2
2
TIME_EV3
3
4
TIME_EV4
0: Time event is OFF
1: Time event is ON
5
TIME_EV5
6
TIME_EV6
7
8
TIME_EV7
0: Time event is OFF
1: Time event is ON
9
TIME_EV8
10 to 15
Bit Configuration of D2041: TIME_EV_2 (Time event status 2)
0
TIME_EV9
0: Time event is OFF
1: Time event is ON
1
TIME_EV10
2
TIME_EV11
3
4
TIME_EV12
0: Time event is OFF
1: Time event is ON
5
TIME_EV13
6
TIME_EV14
7
8
TIME_EV15
0: Time event is OFF
1: Time event is ON
9
TIME_EV16
10 to 15
D2044 to D2049
Register
No.
Description
Range and meaning of value
D2044
SEG_USE
Number of segments contained in the selected
pattern
0 to 99
D2045
NOW_RCY
Number of repetitions of the pattern in operation
0 to 999
D2046
REM_RCY
Number of repetitions of the pattern in operation
0 to 999
D2047
ALL_RCY
Remaining number of repetitions of the pattern in
operation
0 to 1000
D2048
NOW_RST
Repeat Start number of the current segment
1 to 99
D2049
NOW_REN
Repeat End number of the current segment
1 to 99