8-84
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
DI Function Setting (D5901 to D6200)
Register
No.
Description
Range and meaning of value
D5901
A/M-D
*1
AUTO/MAN switch
Set an I relay number of contact input.
0: OFF (Disable)
Standard terminals
DI1: 5025, DI2: 5026
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093
D5902
R/L_L1-D
*1
REMOTE/LOCAL switch
D5903
D5904
S/R-D
*1
STOP/RUN switch
D5905
D5906
AUTO-D
*1
Switch to AUTO
D5907
MAN-D
*1
Switch to MAN
D5908
R
EM_L1-D
*1
Switch to REMOTE
D5909
LCL_L1-D
*1
Switch to LOCAL
D5910 to D5911
D5912
ADV-D
*1
Advance of segment
D5913
HOLD-D
*1
Switch to HOLD (Start of hold-mode
operation)
D5914
AT-D
*1
A
uto-tuning START/STOP switch
D5915 to D5919
D5920
LAT-D
*1
Latch release
D5921
LCD-D
*1
LCD backlight ON/OFF switch
D5922
MG1-D
*1
Message display interruption 1
D5923
MG2-D
*1
Message display interruption 2
D5924
MG3-D
*1
Message display interruption 3
D5925
MG4-D
*1
Message display interruption 4
D5926
PRG-D
*1
Switch to PROG (Start of program operation)
D5927
RST-D
*1
Switch to RESET (Stop of program operation)
D5928
LOC-D
*1
Switch to LOCAL (LSP) (Start of local-mode operation)
D5929
D5930
P/R-D
*1
PROG/RESET switch
D5931
P/L-D
*1
PROG/LOCAL (LSP) switch
D5932
WAIT-D
*1
Wait ON/OFF switch
D5933
A/M_L1-D
*1
AUTO/MAN switch
D5934 to D5935
D5936
P/H-D
*1
PROG/HOLD switch
D5937
PVRW_L1-D
*1
PV red/white switch
D5938
D5939
S.HLD-D
*1
Switch to HOLD for synchronized program
operation
D5940 to D5940
D5941
SP.BC
Bit changing method of SP number
0: Status switch 1
(Operation by key keystrokes or via
communication is enabled according to the
conditions.)
1: Status switch 2
(Operation by key keystrokes or via
communication is disabled.)
D5942
SP.B0
Bit-0 of SP number
Set an I relay number of contact input.
0: OFF (Disable)
Standard terminals
DI1: 5025, DI2: 5026
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093
D5943
SP.B1
Bit-1 of SP number
D5944
SP.B2
Bit-2 of SP number
D5945 to D5946
*1: Same parameter exists in other menu. “-D” is added to the end of the parameter in DI.SL menu.