3-18
IM 05P07A01-01EN
68 Specify monitor
Function
The register No. specified at random can be specified for monitoring.
•The maximum number of registers that can be specified for monitoring is 100.
• For details on the response format at an error, see
“●
Response in an error state” in
“3.1.3 Configuration of Responses (response from UTAdvanced).”
• Broadcasting can be specified. No response is returned when broadcasting is specified.
• When the power supply is turned off, the register specified by “specify monitor” will be
erased. If the power supply is turned off, specify the register by “specify monitor” again.
Message (during normal operation)
Element
Message start
mark (:)
Address No.
(ADR)
Functioncode
(0x44)
Number of
monitor-specified
register
Byte
count(Note 1)
Number of bytes in RTU mode
None
1
1
2
1
Number of bytes in ASCII
mode
1
2
2
4
2
Continuation of message
Monitor-
specified
Register No. 1
• • •
Monitor-specified
Register No. n
Error check
Message
end mark
(CR+LF)
2
• • •
2
2
None
4
• • •
4
2
2
Response (during normal operation)
Element
Message start
mark (:)
Address No.
(ADR)
Function code
(0x44)
Byte count
(Note 1)
Error check
Message
end mark
(CR+LF)
Number of bytes in RTU mode
None
1
1
1
2
None
Number of bytes in ASCII
mode
1
2
2
2
2
2
Note 1: Byte count = 2 x number of specify monitor registers
69 Monitoring
Function
The content of the register specified for monitoring by function code “68” is read.
• For details on the response format at an error, see
“●
Response in an error state” in
“3.1.3 Configuration of Responses (response from UTAdvanced).”
Message (during normal operation)
Element
Message start
mark (:)
Address No.
(ADR)
Function code
(0x45)
Error check
Message
end mark
(CR+LF)
Number of bytes in RTU mode
None
1
1
2
None
Number of bytes in ASCII
mode
1
2
2
2
2
Response (during normal operation)
Element
Message start
mark (:)
Address No.
(ADR)
Function code
(0x45)
Byte count
(Note 1)
Register
content
• • •
Number of bytes in RTU mode
None
1
1
1
2
• • •
Number of bytes in ASCII
mode
1
2
2
2
4
• • •
Continuation of response
Register
content
Error check
Message end
mark (CR+LF)
2
2
None
4
2
2
Note 1: Byte count = 2 x number of registers of monitoring
3.1 Modbus Communication