Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Description
Range and meaning of value
D4653
RP1_L2
Reference point 1
Set reference points at which switching is carried
out between groups
of PID constants according to the given temperature
zone.
0.0 to 100.0% of PV input range (EU)
(RP1 ≤ RP2 ≤ RP3)
D4654
RP2_L2
Reference point 2
D4655
RP3_L2
Reference point 3
D4656 to D4659
D4660
RHY_L1
Zone PID switching hysteresis
Hysteresis can be set for switching at a reference
point.
0.0 to 10.0% of PV input range span (EUS)
D4661
RDV_L1
Reference deviation
Set a deviation from SP. The PID for reference
deviation is used if there is a larger deviation than
the preset reference deviation.
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)