6-133
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Segment Data Setting (D8101 to D8200)
Register
No.
Ref.
No.
H No.
Register
symbol
R/W
Description
Range and meaning of value
D8101 48101 1FA4
PTNO._C
R/W Program pattern number selection 0: Not select program pattern
1 to 30
D8102 48102 1FA5
SEGNO._C
R/W Segment number designation
(0)
1 to 99
D8103 48103 1FA6
TSP_L1
R/W
Loop-1 final target setpoint
0.0 to 100.0% of PV input range (EU) (Setting
range: P.RL to P.RH)
D8104 48104 1FA7
TSP_L2
R/W
Loop-2 final target setpoint
D8105 48105 1FA8
TIME
R/W Segment time setting
Unregistered (65535)
0 to 59999 (minute or second)
* Setting available for the parameter SEG.
T=TIME.* Use the parameter TMU to set the
time unit.
(Common in the instrument.)
* If the setting is 0.00, TSP changes in stepwise
after one control period.
D8106 48106 1FA9
TM.RT
R/W Segment ramp-rate setting
Unregistered (65535)
Ramp: 0.0 to 100.0% of PV input range span
(EUS) / 1 hour or 1 minute
Soak: 0 to 59999 (minute or second)
* Setting available for the parameter SEG.
T=RAMP.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
Per 1 hour: TMU=HH.MM, Per 1 minute:
TMU=MM.SS
* If it is set to 0.0% of the input range span, or
the segment time 0.00, the program moves to
the next segment after one control period.
D8107 48107 1FAA
S.PID
R/W Segment PID number selection
1 to 8
* PID number can be set when the parameter
“ZON = 0.”
D8108 48108 1FAB
JC
R/W Junction code
0: CONT (Switching for continuation)
1: HOLD (Hold-on switching (the controller
holds the end-of-segment setpoint when the
segment is completed, to perform control)).
2: LOC (Local-mode switching (the controller
switches to a local setpoint when the segment
is completed)).
3: REM (Remote-mode switching (the controller
switches to a remote setpoint when the
segment is completed)).
11 to 15: W.SW1 to W.SW5 (Wait during
switching between segments).
16 to 20: W.IV1 to W.IV5 (Wait within a segment
interval).
21 to 25: W.SL1 to W.SL5 (Segment switching
(the controller switches to a local setpoint
when the segment is completed after
release.)) (5 groups)
26 to 30: W.SR1 to W.SR5 (Segment switching
(the controller switches to a remote setpoint
when the segment is completed after
release.)) (5 groups)
31 to 60: PLK.1 to PLK.30 (Linked to patterns 1
to 30.)