6.4 UT55A/UT52A/UP55A D Registers
Loop-1 / Loop-2 Operation Mode and Loop-1 / Loop-2 Alarm Setpoint Setting for UP55A (D2301 to D2400)
Register
No.
Description
Range and meaning of value
D2301
A.M
AUTO/MAN switch
0: AUTO (Automatic mode)
1: MAN (Manual mode)
Effective for the control modes except for cascade
control and cascade secondary-loop control.
D2302
D2303
C.A.M
CAS/AUTO/MAN switch
0: AUTO (Automatic mode)
1: MAN (Manual mode)
2: CAS (Cascade mode)
Effective for cascade control mode and cascade
secondary-loop control mode.
D2304
S.R
STOP/RUN switch
0: RUN (Run mode)
1: STOP (Stop mode)
Preset output (PO) is generated in STOP mode.
Default: Not displayed. STOP/RUN switch is
assigned to contact input.
D2305
D2306
R.L_L1
Loop-1 REMOTE/LOCAL switch
0: LCL (Local mode)
1: REM (Remote mode)
Select a remote input method for acquiring
the target setpoint from remote input, program
operation, or communication using the parameter
RMS.
D2307
R.L_L2
Loop-2 REMOTE/LOCAL switch
0: LCL (Local mode)
1: REM (Remote mode)
Select a remote input method for acquiring
the target setpoint from remote input, program
operation, or communication using the parameter
RMS.
D2308
AT_L1
Loop-1 auto-tuning switch
0: OFF (Disable)
1 to 8: Perform auto-tuning. Tuning result is stored
in the specified numbered PID.
9: R (Tuning result is stored in the PID for reference
deviation.)
D2309
AT_L2
Loop-2 auto-tuning switch
D2310 to D2311
D2312
SPNO.
SP number selection
1 to 8 (Depends on the setup parameter SPGR.
setting.)
D2313
D2314
TRK_ON_L1
Output tracking status
0: OFF
1: ON
D2315
D2316
MODE
Operation mode
(Start/stop of program operation /
start of local-mode operation / start of
remote-mode operation)
0: RESET (Stop of program operation)
1: PROG (Start of program operation)
2: LOCAL (Start of local-mode operation)
3: REM (Start of remote-mode operation)
D2317
HOLD
Pause/cancel release of program
operation
Display during program operation.
0: OFF (Cancel release (Program operation
restart))
1: ON (Pause)
D2318
ADV
Advance of segment
Display during program operation.
Set as “ADV = 1 (ON)” to advance from the current
segment to the next segment.
D2319
A.M_L1
Loop-1 AUTO/MAN switch
0: AUTO (Automatic mode)
1: MAN (Manual mode)
D2320
A.M_L2
Loop-2 AUTO/MAN switch
D2321
L.C
LOCA L(LSP)/CAS switch
0: CAS (Cascade mode)
1: LSP (Local mode))
D2322
PTNO.
Program pattern number selection
0: Not select program pattern
1 to 30
D2323 to D2330