8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Description
Range and meaning of value
D5026
ZON_L2
Loop-2 zone PID selection
If set to “SP group number selection,” allows PID
constants to be selected for each SP group.
If set to “Zone PID selection,” automatically selects
PID constants according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)
D5027 to D5100
Input Setting (D5101 to D5300)
Register
No.
Description
Range and meaning of value
D5101
IN
PV input type
0: OFF (Disable)
1: K1 (-270.0 to 1370.0°
C
/ -450.0 to 2500.0 F)
2: K2 (-270.0 to 1000.0°C / -450.0 to 2300.0 F)
3: K3 (-200.0 to 500.0°C / -200.0 to 1000.0 F)
4: J (-200.0 to 1200.0°C / -300.0 to 2300.0 F)
5: T1 (-270.0 to 400.0°C / -450.0 to 750.0 F)
6: T2 (0.0 to 400.0°C / -200.0 to 750.0 F)
7: B (0.0 to 1800.0°C / 32 to 3300 F)
8: S (0.0 to 1700.0°C / 32 to 3100 F)
9: R (0.0 to 1700.0°C / 32 to 3100 F)
10: N (-200.0 to 1300.0°C / -300.0 to 2400.0 F)
11: E (-270.0 to 1000.0°C / -450.0 to 1800.0 F)
12: L (-200.0 to 900.0°C / -300.0 to 1600.0 F)
13: U1 (-200.0 to 400.0°C / -300.0 to 750.0 F)
14: U2 (0.0 to 400.0°C / -200.0 to 1000.0 F)
15: W (0.0 to 2300.0°C / 32 to 4200 F)
16: PL2 (0.0 to 1390.0°C / 32.0 to 2500.0 F)
17: P2040 (0.0 to 1900.0°C / 32 to 3400 F)
18: WRE (0.0 to 2000.0°C / 32 to 3600 F)
30: JPT1 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
31: JPT2 (-150.00 to 150.00°C / -200.0 to 300.0 F)
35: PT1 (-200.0 to 850.0°C / -300.0 to 1560.0 F)
36: PT2 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
37: PT3 (-150.00 to 150.00°C / -200.0 to 300.0 F)
40: 0.4-2V (0.400 to 2.000 V)
41: 1-5V (1.000 to 5.000 V)
42: 4-20 (4.00 to 20.00 mA)
50: 0-2V (0.000 to 2.000 V)
51: 0-10V (0.00 to 10.00 V)
52: 0-20 (0.00 to 20.00 mA)
55: -1020 (-10.00 to 20.00 mV)
56: 0-100 (0.0 to 100.0 mV)
*W: W-5% Re/W-26% Re(Hoskins Mfg. Co.), ASTM E988
WRE: W97Re3-W75Re25
D5102
UNIT
PV input unit
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
D5103
DP
PV input decimal point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
D5104
RH
M
aximum value of PV input range
Depends on the input type.
- For temperature input -
Set the temperature range that is actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current signal that is applied.
The scale across which the voltage / current signal is actually
controlled should be set using the maximum value of input
scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
D5105
RL
Minimum value of PV input range
D5106
S
DP
P
V input scale decimal point position
Same as D5103
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...