
14-34
IM 05P07A01-01EN
14.4 UT75A D Registers
Loop-1 Alarm Function Setting (D2801 to D2900)
Register
No.
Description
Range and meaning of value
D2801
AL1.T_L1
Alarm-1 type
A
L1.T_L1 to AL8.T_L1
0: Disable
1: PV high limit
2: PV low limit
3: SP high limit
4: SP low limit
5: Deviation high limit
6: Deviation low limit
7: Deviation high and low limits
8: Deviation within high and low limits
9: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
21: Analog input PV2 high limit
22: Analog input PV2 low limit
23: Analog input AIN2 high limit
24: Analog input AIN2 low limit
25: Analog input AIN4 high limit
26: Analog input AIN4 low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
32: Deviation(%) high limit
33: Deviation(%) low limit
34: Deviation(%) high and low limits
35: Deviation(%) within high and low limits
36: Target SP deviation(%) high limit
37: Target SP deviation(%) low limit
38: Target SP deviation(%) high and low limits
39: Target SP deviation(%) within high and low limits
A
L1.W_L1 to AL8.W_L1
0: Without Stand-by action
1: With Stand-by action
A
L1.D_L1 to AL8.D_L1
0
: Alarm output: Energized
1: A
larm output: De-energized
A
L1.L_L1 to AL8.L_L1
0
: OFF
1: Latch 1
2: Latch 2
3: Latch 3
4: Latch 4
When the UTAdvanced parameter is set by key
stroke, the alarm type, stand-by action, energized/
de-energized, and latch comprise one parameter.
D2802
AL1.W_L1
Alarm-1 stand-by action
D2803
AL1.D_L1
Alarm-1
energized/de-energized
D2804
AL1.L_L1
Alarm-1 latch
D2805
AL2.T_L1
Alarm-2 type
D2806
AL2.W_L1
Alarm-2 stand-by action
D2807
AL2.D_L1
A
larm-2 energized/de-energized
D2808
AL2.L_L1
Alarm-2 latch
D2809
AL3.T_L1
Alarm-3 type
D2810
AL3.W_L1
Alarm-3 stand-by action
D2811
AL3.D_L1
A
larm-3 energized/de-energized
D2812
AL3.L_L1
Alarm-3 latch
D2813
AL4.T_L1
Alarm-4 type
D2814
AL4.W_L1
Alarm-4 stand-by action
D2815
AL4.D_L1
A
larm-4 energized/de-energized
D2816
AL4.L_L1
Alarm-4 latch
D2817
AL5.T_L1
Alarm-5 type
D2818
AL5.W_L1
Alarm-5 stand-by action
D2819
AL5.D_L1
A
larm-5 energized/de-energized
D2820
AL5.L_L1
Alarm-5 latch
D2821
AL6.T_L1
Alarm-6 type
D2822
AL6.W_L1
Alarm-6 stand-by action
D2823
AL6.D_L1
A
larm-6 energized/de-energized
D2824
AL6.L_L1
Alarm-6 latch
D2825
AL7.T_L1
Alarm-7 type
D2826
AL7.W_L1
Alarm-7 stand-by action
D2827
AL7.D_L1
A
larm-7 energized/de-energized
D2828
AL7.L_L1
Alarm-7 latch
D2829
AL8.T_L1
Alarm-8 type
D2830
AL8.W_L1
Alarm-8 stand-by action
D2831
AL8.D_L1
A
larm-8 energized/de-energized
D2832
AL8.L_L1
Alarm-8 latch
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...