8-71
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Description
Range and meaning of value
D5107
SH
Maximum value of PV input scale
-
19999 to 30000, (SL<SH), | SH - SL | ≤ 30000
D5108
SL
Minimum value of PV input scale
D5109
BSL
PV input burnout action
0: OFF (Disable)
1: UP (Upscale)
2: DOWN (Downscale)
D5110
RJC
PV input reference junction
compensation
0: OFF (RJC OFF)
1: ON (RJC ON)
D5111
ERJC
PV input external RJC setpoint
-10.0 to 60.0°C
D5112
A.BS
PV analog input bias
-100.0 to 100.0% of PV input range span (EUS)
D5113
A.FL
PV analog input filter
0: OFF
1 to 120 s
D5114 to D5200
D5201
P.UNI_L1
Control PV input unit
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
D5202
P.DP_L1
Control PV input decimal point
position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
D5203
P.RH_L1
Maximum value of control PV input
range
-
19999 to 30000, (P.RL<P.RH), | P.RH - P.RL | ≤ 30000
D5204
P.RL_L1
Minimum value of control PV input
range
D5205 to D5209
D5210
SPH_L1
SP high limit
0
.0 to 100.0% of PV input range (EU), (SPL<SPH)
D5211
SPL_L1
SP low limit
D5210 to D5300
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...