2-6
IM 05P07A01-01EN
2.2 Setting Communication Write Permit
Writing to registers via all communication protocols can be permitted and prohibited.
(When the writing is being prohibited, the response returns as "normal" if the
communication is performed, but the writing is not performed.)
However, communication using the light-loader (on the front panel) is possible.
Writing to registers via communication is possible only when the parameter COM.W
(communication write enable/disable) in the KLOC menu is set to OFF (enable).
Setting Display
Parameter Setting Display
UT75A/UT55A/UT35A/UP55A/UP35A:
Operation Display >
PARAMETER
and
Left arrow
keys
simultaneously for 3 seconds (to the [
CTL
] Menu Display) >
Right
arrow
key (to the [
KLOC
] Menu Display) >
SET/ENTER
key (The
COM.W parameter is displayed.)
UT52A/UT32A/UM33A:
Operation Display >
PARA
and
Left arrow
keys simultaneously for
3 seconds (to the [
CTL
] Menu Display) >
Right arrow
key (to the
[
KLOC
] Menu Display) >
SET/ENTER
key (The COM.W parameter is
displayed.)
Setting Details
Parameter
symbol
Name
Setting range
Menu symbol Initial value
COM.W
Communication
write enable/
disable
OFF: Enable (0)
KLOC
OFF (0)
ON: Disable (1)
Note: Figures in parentheses "( )" are values to be set when performing communication.