8-69
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Control Function Setting (D5001 to D5100)
Register
No.
Description
Range and meaning of value
D5001 to D5002
D5003
CNT_L1
Control type
0: PID (PID control)
1: ONOF (ON/OFF control (1 point of hysteresis))
2: ONOF2 (ON/OFF control (2 points of hysteresis))
3: 2P2L (Two-position two-level control) *1
4: H/C (Heating/cooling control) *2
*1: For UT35A/UT32A only.
*2: All models except UT32A-D.
D5004
D5005
ALG_L1
PID control mode
0: Standard PID control mode
1: Fixed-point control mode
Select “Fixed-point control mode” for pressure or
flow rate control.
D5006
D5007
SPGR.
Number of SP groups
Set a number of SP groups to use.
1 to 4
D5008
D5009
ALNO._L1
Number of alarms
1 to 4
D5010
ALNO._L2
Loop-2 number of alarms
1 to 4
D5011
D5012
ZON
Zone PID selection
UT35A/UT32A
If set to “SP group number selection,” allows PID
constants to be selected for each SP group.
If set to “Zone PID selection,” automatically selects
PID constants according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)
UP35A
0: Segment PID selection
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by target SP)
4: Zone PID selection (selection by SP)
5: Local PID selection
* If set to “Segment PID selection,” allows PID
constants to be selected for each segments.
* If set to “Zone PID selection,” automatically
selects PID constants according to the range set
in the Reference point.
* If set to “Local PID selection,” local PID is selected
irrespective of the operation modes.
D5013
D5014
PIDG.
Number of PID groups
Set a number of PID groups to use.
1 to 4
D5015
D5016
SEG.T
Segment setting method
0: TIME (Segment time setting)
1: TM.RT (Segment ramp-rate setting)
* Note: A change of setting deletes a program
pattern.
D5017
TMU
Program time unit
0: HH.MM (hour.minute)
1: MM.SS (minute.second)
D5018 to D5025