8-79
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Description
Range and meaning of value
D5719
BAR1
Bar-graph display registration
0: Disable
1: OUT, Heating-side OUT, Internal value in Position
proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
19 to 22: Disable
23: Time event and alarm status
D5720
D5721
BDV_L1
Bar-graph deviation display band
0
.0 to 100.0% of PV input range span (EUS)
D5722
D5723
EV1_L1
EV1 display condition registration
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm occurs)
4530: Heater break alarm 2 (Lit when the alarm occurs)
5025 to 5026: Link to DI1-DI2 (Lit when the contact is closed)*
5041 to 5045: Link to DI11-DI15 (E1-terminal area) (Lit
when the contact is closed)*
5089 to 5093: Link to DI41-DI45 (E4-terminal area) (Lit
when the contact is closed)*
5153 to 5155: Link to AL1-AL3 (Lit when the contact is closed)*
5169 to 5173: Link to DO11-DO15 (E1-terminal area) (Lit
when the contact is closed)*
5217 to 5221: Link to DO41-DO45 (E4-terminal area) (Lit
when the contact is closed)*
*: Initial value. The contact action changes by the
setting of each "contact type" parameter.
4785: Link to PV event 1/local event-1 (Lit when occurs) **
4786: Link to PV event 2/local event-2 (Lit when occurs) **
4817: Link to time event 1 (Lit when occurs) **
4818: Link to time event 2 (Lit when occurs) **
4819: Link to time event 3 (Lit when occurs) **
4821: Link to time event 4 (Lit when occurs) **
**: For UP35A only
For other functions, see the Chapter 9 Functions and
Applications of I Relays (for UT35A/UT32A/UP35A).
D5724
EV2_L1
EV2 display condition registration
D5725
EV3_L1
EV3 display condition registration
D5726
EV4_L1
EV4 display condition registration
D5727 to D5738
D5739
PV.D
PV display area ON/OFF
0: OFF (Nondisplay)
1: ON (Display)
D5740
SP.D
Setpoint display area ON/OFF
D5741
STS.D
Status display area ON/OFF
D5742
SPD
Scroll speed
(Slow) 1 to 8 (Quick)
D5743
GUID
Guide display ON/OFF
0: OFF (Nondisplay)
1: ON (Display)