6.6 GREEN Series Compatible D Registers
D0955 to D0958: Loop-2 alarm-1 type to alarm-4 type
UTAdvanced
Register
No.
Description
Range and meaning of value
D0955
AL1.T_L2
Loop-2 alarm-1 type
00: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
21: Analog input RSP high limit
22: Analog input RSP low limit
23: Analog input AIN2 high limit
24: Analog input AIN2 low limit
25: Analog input AIN4 high limit
26: Analog input AIN4 low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
D0956
AL2.T_L2
Loop-2 alarm-2 type
D0957
AL3.T_L2
Loop-2 alarm-2 type
D0958
AL4.T_L2
Loop-2 alarm-4 type
GREEN Series
Register
No.
Description
Range and meaning of value
D0955
AL1.1
Loop-2 alarm-1 type
OFF (0), 1 to 20, 25 to 31, 33 to 38, 43 to 48
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
For other alarm types, see “Changing Alarm Type” of GREEN series (UT551,
UT550, UT520) User
’
s manual.
D0956
AL2.1
Loop-2 alarm-2 type
OFF (0), 1 to 20, 25 to 31, 33 to 38, 43 to 48
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
For other alarm types, see “Changing Alarm Type” of GREEN series (UT551,
UT550, UT520) User
’
s manual.
D0957
AL3.1
Loop-2 alarm-3 type
D0958
AL4.1
Loop-2 alarm-4 type