
8-32
IM 05P07A01-01EN
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Alarm Function Setting (D2801 to D2900)
Register
No.
Description
Range and meaning of value
D2801
AL1.T_L1
Alarm-1 type
A
L1.T_L1 to AL8.T_L1
0: Disable
1: PV high limit
2: PV low limit
3: SP high limit
4: SP low limit
5: Deviation high limit
6: Deviation low limit
7: Deviation high and low limits
8: Deviation within high and low limits
9: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
A
L1.W_L1 to AL4.W_L1
0: Without Stand-by action
1: With Stand-by action
A
L1.D_L1 to AL4.D_L1
0
: Alarm output: Energized
1: A
larm output: De-energized
A
L1.L_L1 to AL4.L_L1
0
: OFF
1: Latch 1
2: Latch 2
3: Latch 3
4: Latch 4
When the UTAdvanced parameter is set by key
stroke, the alarm type, stand-by action, energized/
de-energized, and latch comprise one parameter.
D2802
AL1.W_L1
Alarm-1 stand-by action
D2803
AL1.D_L1
Alarm-1
energized/de-energized
D2804
AL1.L_L1
Alarm-1 latch
D2805
AL2.T_L1
Alarm-2 type
D2806
AL2.W_L1
Alarm-2 stand-by action
D2807
AL2.D_L1
A
larm-2 energized/de-energized
D2808
AL2.L_L1
Alarm-2 latch
D2809
AL3.T_L1
Alarm-3 type
D2810
AL3.W_L1
Alarm-3 stand-by action
D2811
AL3.D_L1
A
larm-3 energized/de-energized
D2812
AL3.L_L1
Alarm-3 latch
D2813
AL4.T_L1
Alarm-4 type
D2814
AL4.W_L1
Alarm-4 stand-by action
D2815
AL4.D_L1
A
larm-4 energized/de-energized
D2816
AL4.L_L1
Alarm-4 latch
D2817 to D2832
D2833
VT1_L1
PV velocity alarm time setpoint 1
1 to 5999 (second)
D2834
VT2_L1
PV velocity alarm time setpoint 2
D2835
VT3_L1
PV velocity alarm time setpoint 3
D2836
VT4_L1
PV velocity alarm time setpoint 4
D2837 to D2840
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...