14-11
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Bit Configuration of D2012:
LA.ER
(Ladder error status)
Bit
Symbol
Event
0
LAD_ERR
Corrupted ladder program
1
LAD_OVER
Ladder calculation overflow
2
LAD_P_ERR
Ladder program error
3
4
LD100_OVER
Load factor over 100%
5
LD200_OVER
Load factor over 200% (Forced end)
6 to 15
Bit Configuration of D2013: ALM_L2 (Loop-2 alarm-1 to alarm-8 status)
Bit
Symbol
Event
0
ALM1_L2
‘1’ when Loop-2 alarm 1 is ON; ‘0’ when OFF
1
ALM2_L2
‘1’ when Loop-2 alarm 2 is ON; ‘0’ when OFF
2
ALM3_L2
‘1’ when Loop-2 alarm 3 is ON; ‘0’ when OFF
3
4
ALM4_L2
‘1’ when Loop-2 alarm 4 is ON; ‘0’ when OFF
5
ALM5_L2
‘1’ when Loop-2 alarm 5 is ON; ‘0’ when OFF
6
ALM6_L2
‘1’ when Loop-2 alarm 6 is ON; ‘0’ when OFF
7
8
ALM7_L2
‘1’ when Loop-2 alarm 7 is ON; ‘0’ when OFF
9
ALM8_L2
‘1’ when Loop-2 alarm 7 is ON; ‘0’ when OFF
10 to 15
Bit Configuration of D2018:
PV2.E_L2
(Loop-2 PV input error status)
Bit
Symbol
Event
0
PVBO_L2
Loop-2 PV input burnout error
1
PV2BO_L2
Loop-2 PV2 input burnout error
2
CPV2BO_L2
Burnout error when the Loop-2 PV2 input is used for control.
3
4
PVPOVER_L2
Loop-2 PV input over-scale
5
PVMOVER_L2
Loop-2 PV input under-scale
6 to 13
14
ATERR_L2
Loop-2 auto-tuning timeout error
15
D2019 to D2023
Register
No.
Description
Range and meaning of value
D2019
PV_L2
Loop-2 measurment value
-5.0 to 105.0% of PV input range (EU)
D2020
CSP_L2
Loop-2 control setpoint
0.0 to 100.0% of PV input range (EU) (Setting
range: SPL to SPH)
D2021
OUT_L2
Loop-2 control output
-5.0 to 105.0%
D2022
H.OUT_L2
Heating-side control output
-5.0 to 105.0% (In Heating/cooling control: 0.0 to
105.0%)
D2023
C.OUT_L2
Cooling-side control output
0.0 to 105.0%
Bit Configuration of D2024: MOD_L2 (Loop-2 operation mode status)
Bit
Symbol
Event
0
A.M_L2
0: AUTO, 1: MAN
1
R.L_L2
0: Local, 1: Remote
2
S.R_L2
0: Run, 1: Stop
3 to 13
14
AT_L2_ON
0: Auto-tuning is OFF, 1: Auto-tuning is ON
15