12-7
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A-L)
12
12.4 UT35A-L D Registers
Process Data Area
Some of the D registers represent multiple events such as errors and status depending
on combinations of bits in the register.
In the following tables, if an event indicated by a specific bit occurs, the state of that bit
changes to “1.”
If no event occurs, the state of that bit is “0.” Blank lines in each table indicate unused
bits.
Process Data (D2001 to D2100)
Bit Configuration of D2001:
AD1.E
(A/D converter error status 1)
Bit
Symbol
Event
0
ADERR
PV input A/D converter error
1 to 4
5
RJCERR
PV input RJC error
6 to 7
8
ADBO
PV input burnout error
9 to 15
Bit Configuration of D2002:
PV1.E_L1
(PV input error status)
Bit
Symbol
Event
0
PVBO_L1
PV input burnout error
1 to 3
4
PVPOVER_L1
PV input over-scale
5
PVMOVER_L1
PV input under-scale
6 to 15
D2003 to D2004
Register
No.
Description
Range and meaning of value
D2003
PV_L1
Measurment value
-5.0 to 105.0% of PV input range (EU)
D2004
CSP_L1
Control setpoint
0.0 to 100.0% of PV input range (EU) (Setting
range: SPL to SPH)
Bit Configuration of D2008: MOD_L1 (Operation mode status)
Bit
Symbol
Event
0
1 to 11
12
EXD
1: Exceeded
13
OUT
0: Output relay OFF, 1: Output relay ON
14 to 15
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...