6-25
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Description
Range and meaning of value
D2331
C.RSP_L1
Loop-1 communication remote
setpoint
0.0 to 100.0% of PV input range (EU)
D2332
C.RSP_L2
Loop-2 communication remote
setpoint
D2333
MOUT_L1
Loop-1 heating-side control output in
MAN mode
0.0 to 105.0% (Standard type: -5.0 to 105.0%)
D2334
MOUTc_L1
Loop-1 cooling-side control output in
MAN mode
0.0 to 105.0%
D2335
MOUT_L2
Loop-2 heating-side control output in
MAN mode
0.0 to 105.0% (Standard type: -5.0 to 105.0%)
D2336
MOUTc_L2
Loop-2 cooling-side control output in
MAN mode
0.0 to 105.0%
D2337
H.SP_L1
Loop-1 SP for HOLD state
0.0 to 100.0% of PV input range (EU)
D2338
H.SP_L2
Loop-2 SP for HOLD state
D2339
H.TSP_L1
Loop-1 TSP for HOLD state
D2340
H.TSP_L2
Loop-2 TSP for HOLD state
D2341
H.TM
HOLD time
0 to 59999 (minute or second)
* Use the parameter TMU to set the time unit.
D2343
SST
Start-of-program segment number
1 to 99
The setting value returns to “1” when the program
operation (PROG) changes into RESET, LOCAL,
or REM.
D2343
P.FWD
Fast-forwarding of program operation
1: Normal
2: Twice
5: Five times
10: Ten times
20: Twenty times
* Use this function when checking the program
pattern setting. Only Segment time and Time
event can be faster.
* The operation returns to the normal speed after
fast-forwarding.
D2344 to D2350
D2351
A1_L1_1
Loop-1 Alarm-1 setpoint
These alarms work irrespective of the operation
mode.
Set a display value of setpoint of PV alarm, SP
alarm,
deviation alarm, output alarm, or velocity alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type.
D2352
A2_L1_1
Loop-1 Alarm-2 setpoint
D2353
A3_L1_1
Loop-1 Alarm-3 setpoint
D2354
A4_L1_1
Loop-1 Alarm-4 setpoint
D2355
A5_L1_1
Loop-1 Alarm-5 setpoint
D2356
A6_L1_1
Loop-1 Alarm-6 setpoint
D2357
A7_L1_1
Loop-1 Alarm-7 setpoint
D2358
A8_L1_1
Loop-1 Alarm-8 setpoint
D2359 to D2360
D2361
A1_L2_1
Loop-2 Alarm-1 setpoint
D2362
A2_L2_1
Loop-2 Alarm-2 setpoint
D2363
A3_L2_1
Loop-2 Alarm-3 setpoint
D2364
A4_L2_1
Loop-2 Alarm-4 setpoint
D2365
A5_L2_1
Loop-2 Alarm-5 setpoint
D2366
A6_L2_1
Loop-2 Alarm-6 setpoint
D2367
A7_L2_1
Loop-2 Alarm-7 setpoint
D2368
A8_L2_1
Loop-2 Alarm-8 setpoint
D2369 to D2400
Free Area (D2401 to D2500)
Register
No.
Description
Range and meaning of value
D2401 to D2500
Free area