14-90
IM 05P07A01-01EN
14.4 UT75A D Registers
Key Operation Setting, Display Function Setting, and SELECT Display Setting (D5701 to D5800)
Register
No.
Description
Range and meaning of value
D5701
F1
*
1
User function key-1 action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
2: C/A/M (CAS/AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
4: R/L2 (Loop-2 REM/LCL switch)
5: S/R (STOP/RUN switch)
6: CAS (Switch to CAS)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
9: REM1 (Switch to REM)
10: LCL1 (Switch to LCL)
11: REM2 (Switch to Loop-2 REM)
12: LCL2 (Switch to Loop-2 LCL)
13: STOP (Switch to STOP)
14: RUN (Switch to RUN)
17: AT (Auto-tuning)
18: LTUP (LCD brightness UP)
19: LTDN (LCD brightness DOWN)
20: BRI (Adjust LCD brightness)
21: LCD (LCD backlight ON/OFF switch)
22: LAT (Latch release)
23: PID (PID tuning switch)
34: Start of hold-mode operation
35: Advance of segment
36: Home display switch
37: Loop-1/Loop-2 display switch
38: Displaying loop AUTO/MAN switch
39: Displaying loop REM/LCL switch
40: Displaying loop STOP/RUN switch
41: Switch to AUTO displaying loop
42: Switch to MAN displaying loop
43: Switch to REM displaying loop
44: Switch to LCL displaying loop
45: Switch to STOP displaying loop
46: Switch to RUN displaying loop
47: Displaying loop auto-tuning
48: PID tuning switch displaying loop
49: Start of program operation
50: Stop of program operation
Loop-2 setting values are unavalable in Single-loop control.
D5702
F2
*
1
User function key-2 action setting
D5703
Fn
*
1
User function key-n action setting
D5704
A/M-K
*
1
A/M key action setting
0: OFF (Disable)
1: A/M (AUTO/MAN switch)
2: C/A/M (CAS/AUTO/MAN switch)
3: R/L1 (REM/LCL switch)
4: R/L2 (Loop-2 REM/LCL switch)
5: S/R (STOP/RUN switch)
6: CAS (Switch to CAS)
7: AUTO (Switch to AUTO)
8: MAN (Switch to MAN)
D5709 to D5710
D5711
DVB_L1
Loop-1 deviation display band
Permits a change in the span of deviation shown on
the front-panel deviation monitor.
0.0 to 100.0% of PV input range span (EUS)
D5712
D
VB_L2
Loop-2 deviation display band
*1: Same parameter exists in other menu. “-K” is added to the end of the parameter in KEY
menu.