10-34
IM 05P07A01-01EN
10.4 UM33A D Registers
Register
No.
Description
Range and meaning of value
D5201
P.UNI_L1
Control PV input unit
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
D5202
P.DP_L1
Control PV input decimal point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
D5203
P.RH_L1
Maximum value of control PV input range
-
19999 to 30000, (P.RL<P.RH), | P.RH - P.RL | ≤ 30000
D5204
P.RL_L1
Minimum value of control PV input range
D5205 to D5300
Output Setting (D5301 to D5400)
Register
No.
Description
Range and meaning of value
D5301 to D5320
D5321
RTS
Retransmission output type of RET
0: OFF (Disable)
1: P
V1 (PV)
4: L
PS (15 V DC loop power supply)
D5322
RTH
Maximum value of retransmission
output scale of RET
W
hen RTS=1 (PV1), RTL+1digit to 30000
Decimal point position:
RTS=1 (PV1): decimal point position is same as that of PV
input.
D5323
RTL
Minimum value of retransmission
output scale of RET
W
hen RTS=1 (PV1), -19999 to RTH-1digit
Decimal point position:
RTS=1 (PV1): decimal point position is same as that of PV
input.
D5324 to D5334
D5335
RET.H
100% segmental point of RET
current output
-100.0 to 200.0%
D5336
RET.L
0% segmental point of RET current
output
D5337 to D5342
D5343
RET.A
RET current output range
0: 4-20 (4 to 20 mA)
1: 0-20 (0 to 20 mA)
2: 20-4 (20 to 4 mA)
3: 20-0 (20 to 0 mA)
D5344 to D5400
Free Area (D5401 to D5500)
Register
No.
Description
Range and meaning of value
D5401 to 5500
Free area