10-14
IM 05P07A01-01EN
10.4 UM33A D Registers
Alarm Function Setting (D2801 to D2900)
Register
No.
Description
Range and meaning of value
D2801
AL1.T_L1
Alarm-1 type
AL1.T_L1 to AL8.T_L1
0: Disable
1: PV high limit
2: PV low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
AL1.W_L1 to AL8.W_L1
0: Without Stand-by action
1: With Stand-by action
AL1.D_L1 to AL8.D_L1
0: Alarm output: Energized
1: Alarm output: De-energized
AL1.L_L1 to AL8.L_L1
0: OFF
1: Latch 1
2: Latch 2
3: Latch 3
4: Latch 4
When the UTAdvanced parameter is set by key
stroke, the alarm type, stand-by action, energized/
de-energized, and latch comprise one parameter.
D2802
AL1.W_L1
Alarm-1 stand-by action
D2803
AL1.D_L1
Alarm-1 energized/de-energized
D2804
AL1.L_L1
Alarm-1 latch
D2805
AL2.T_L1
Alarm-2 type
D2806
AL2.W_L1
Alarm-2 stand-by action
D2807
AL2.D_L1
Alarm-2 energized/de-energized
D2808
AL2.L_L1
Alarm-2 latch
D2809
AL3.T_L1
Alarm-3 type
D2810
AL3.W_L1
Alarm-3 stand-by action
D2811
AL3.D_L1
Alarm-3 energized/de-energized
D2812
AL3.L_L1
Alarm-3 latch
D2813
AL4.T_L1
Alarm-4 type
D2814
AL4.W_L1
Alarm-4 stand-by action
D2815
AL4.D_L1
Alarm-4 energized/de-energized
D2816
AL4.L_L1
Alarm-4 latch
D2817
AL5.T_L1
Alarm-5 type
D2818
AL5.W_L1
Alarm-5 stand-by action
D2819
AL5.D_L1
Alarm-5 energized/de-energized
D2820
AL5.L_L1
Alarm-5 latch
D2821
AL6.T_L1
Alarm-6 type
D2822
AL6.W_L1
Alarm-6 stand-by action
D2823
AL6.D_L1
Alarm-6 energized/de-energized
D2824
AL6.L_L1
Alarm-6 latch
D2825
AL7.T_L1
Alarm-7 type
D2826
AL7.W_L1
Alarm-7 stand-by action
D2827
AL7.D_L1
Alarm-7 energized/de-energized
D2828
AL7.L_L1
Alarm-7 latch
D2829
AL8.T_L1
Alarm-8 type
D2830
AL8.W_L1
Alarm-8 stand-by action
D2831
AL8.D_L1
Alarm-8 energized/de-energized
D2832
AL8.L_L1
Alarm-8 latch
D2833
VT1_L1
PV velocity alarm time setpoint 1
1 to 5999 (second)
D2834
VT2_L1
PV velocity alarm time setpoint 2
D2835
VT3_L1
PV velocity alarm time setpoint 3
D2836
VT4_L1
PV velocity alarm time setpoint 4
D2837
VT5_L1
PV velocity alarm time setpoint 5
D2838
VT6_L1
PV velocity alarm time setpoint 6
D2839
VT7_L1
PV velocity alarm time setpoint 7
D2840
VT8_L1
PV velocity alarm time setpoint 8