14-79
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Control Function Setting (D5001 to D5100)
Register
No.
Description
Range and meaning of value
D5001
CTLM
Control mode
1: SGL (Single-loop control)
2: CAS1 (Cascade primary-loop control)
3: CAS2 (Cascade secondary-loop control)
4: CAS (Cascade control)
5: BUM (Loop control for backup)
6: PVSW (Loop control with PV switching)
7: PVSEL (Loop control with PV auto-selector)
8: PVHD (Loop control with PV-hold function)
11: Dual-loop control
* When using the ladder program, the control mode
cannot be changed.
D5002
D5003
CNT_L1
Loop-1 control type
0: PID (PID control)
1: ONOF (ON/OFF control (1 point of hysteresis))
2: ONOF2 (ON/OFF control (2 points of hysteresis))
3: 2P2L (Two-position two-level control)
4: H/C (Heating/cooling control)
5: S-PI (Sample PI control)
6: BATCH (Batch PID control)
7: FFPID (Feedforward control)
D5004
CNT_L2
Loop-2 control type
0: PID (PID control)
1: ONOF (ON/OFF control (1 point of hysteresis))
2: ONOF2 (ON/OFF control (2 points of hysteresis))
4: H/C (Heating/cooling control)
D5005
ALG_L1
Loop-1 PID control mode
0: Standard PID control mode
1: Fixed-point control mode
Select “Fixed-point control mode” for pressure or
flow rate control.
D5006
A
LG_L2
Loop-2 PID control mode
D5007
SPGR.
Number of SP groups
Set a number of SP groups to use.
1 to 20
D5008
D5009
ALNO._L1
Loop-1 number of alarms
1 to 8
D5010
ALNO._L2
Loop-2 number of alarms
1 to 8
D5011
D5012
ZON
Zone PID selection
If set to “SP group number selection,” allows PID
constants to be selected for each SP group.
If set to “Zone PID selection,” automatically selects
PID constants according to the range set in the
Reference point.
0: SP group number selection 1
1: Zone PID selection (selection by PV)
2: Zone PID selection (selection by target SP)
3: SP group number selection 2
4: Zone PID selection (selection by SP)
D5013
D5014
PIDG.
Number of PID groups
Set a number of PID groups to use.
1 to 16
D5015 to D5018
D5019
SMP
Input sampling period (control period)
0: 50 (50 ms)
1: 100 (100 ms)
2: 200 (200 ms)
D5020 to D5100