8-19
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT35A/UT32A/UT32A-D/UP35A/UP32A)
8
8.4 UT35A/UT32A/UT32A-D/UP35A/UP32A D Registers
Register
No.
Description
Range and meaning of value
D2133
PO_L1_*
Preset output
Heating-side preset output (in Heating/
cooling control)
In STOP mode, fixed control output can be
generated. In Position proportional control, Valve
opening can be set
-5.0 to 105.0%
D2134
SU.PO_*
Sub-preset output (in Two-position
two-level control)
In STOP mode, fixed sub-control output can be
generated.
0%, 100%
D2135
POc_L1_*
Cooling-side preset output
In STOP mode, cooling-side fixed control output
can be generated.
-5.0 to 105.0%
D2136 to D2150
D2151
SP_L2_*
Same as D2101.
D2152 to D2200
*: 1 to 4, or R
Local-mode Operation Setting for UP35A (D2201 to D2300)
Register
No.
Description
Range and meaning of value
D2201
LSP_L1
Local target setpoint
0.0 to 100.0% of PV input range (EU) (Setting
range: P.RL to P.RH)
D2202
D2203
L.PID
PID number selection for local-mode operation
Set a PID group number to use.
1 to 4
* Available only for the L.PID when ZON = 0 or 5.
* If set to “Local PID selection,” local PID is
selected irrespective of the operation modes.
D2204
L.TY1
Local event-1 type
OFF: Disable
(Energized)
01: PV high limit, 02: PV low limit,
03: SP high limit, 04: SP low limit,
05: Deviation high limit,
06: Deviation low limit,
07: Deviation high and low limits,
08: Deviation within high and low limits,
09: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low limits,
15: OUT high limit, 16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when
the PV high limit is de-energized, the setting is
101.
D2205
L.EV1
Local event-1 setpoint
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, or output alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type
D2206
L.TY2
Local event-2 type
Same as D2204
D2207
L.EV2
Local event-2 setpoint
Same as D2205
D2208 to D2300