14-32
IM 05P07A01-01EN
14.4 UT75A D Registers
Loop-1 SP and Alarm Setpoint Setting of Groups 1 to 8 (D2501 to D2700)
Register
No.
Description
Range and meaning of value
D2501
SP_L1_1
Target setpoint of group 1
0.0 to 100.0% of PV input range (EU) (Setting
range: SPL to SPH)
D2502
SUB_1
Sub-target setpoint (in Two-position
two-level control) of group 1
Set the offset from SP.
-100.0 to 100.0% of PV input range span (EUS)
D2503
PIDN_L1_1
PID number selection of group 1
Set a PID group number to use.
1 to 8 (Depends on the PIDG. setting.)
D2504
A1_L1_1
Alarm-1 setpoint of group 1
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value within the input
range.)
Decimal point position depends on the input type.
D2505
A2_L1_1
Alarm-2 setpoint of group 1
D2506
A3_L1_1
Alarm-3 setpoint of group 1
D2507
A4_L1_1
Alarm-4 setpoint of group 1
D2508
A5_L1_1
Alarm-5 setpoint of group 1
D2509
A6_L1_1
Alarm-6 setpoint of group 1
D2510
A7_L1_1
Alarm-7 setpoint of group 1
D2511
A8_L1_1
Alarm-8 setpoint of group 1
D2512
UPR_L1_1
SP ramp-up rate of group 1
Used to prevent SP from changing suddenly.
Set a ramp-up rate or ramp-down rate per hour or
minute. Set a time unit using the parameter TMU.
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)
D2513
DNR_L1_1
SP ramp-down rate of group 1
D2514 to D2520
D2521 to
D2531
SP_L1_2 to A8_L1_2
Target setpoint of group 2 to Alarm-8
setpoint of group 2
Same as 2501 to D2511
D2532
UPR_L1_2
SP ramp-up rate of group 2
Same as 2512 to D2513
D2533
DNR_L1_2
SP ramp-down rate of group 2
D2534 to D2540
D2541 to
D2551
SP_L1_3 to A8_L1_3
Target setpoint of group 3 to Alarm-8
setpoint of group 3
Same as D2501 to D2511
D2552
UPR_L1_3
SP ramp-up rate of group 3
Same as 2512 to D2513
D2553
DNR_L1_3
SP ramp-down rate of group 3
D2552 to D2560
D2561 to
D2571
SP_L1_4 to A8_L1_4
Target setpoint of group 4 to Alarm-8
setpoint of group 4
Same as D2501 to D2511
D2572
UPR_L1_4
SP ramp-up rate of group 4
Same as 2512 to D2513
D2573
DNR_L1_4
SP ramp-down rate of group 4
D2574 to D2580
D2581 to
D2591
SP_L1_5 to A8_L1_5
Target setpoint of group 5 to Alarm-8
setpoint of group 5
Same as D2501 to D2511
D2592
UPR_L1_5
SP ramp-up rate of group 5
Same as 2512 to D2513
D2593
DNR_L1_5
SP ramp-down rate of group 5
D2594 to D2600
D2601 to
D2611
SP_L1_6 to A8_L1_6
Target setpoint of group 6 to Alarm-8
setpoint of group 6
Same as D2501 to D2511
D2612
UPR_L1_6
SP ramp-up rate of group 6
Same as 2512 to D2513
D2613
DNR_L1_6
SP ramp-down rate of group 6
D2612 to D2620
D2621 to
D2631
SP_L1_7 to A8_L1_7
Target setpoint of group 7 to Alarm-8
setpoint of group 7
Same as D2501 to D2511
D2632
UPR_L1_7
SP ramp-up rate of group 7
Same as 2512 to D2513
D2633
DNR_L1_7
SP ramp-down rate of group 7
D2632 to D2640
D2641 to
D2651
SP_L1_8 to A8_L1_8
Target setpoint of group 8 to Alarm-8
setpoint of group 8
Same as D2501 to D2511
D2652
UPR_L1_8
SP ramp-up rate of group 8
Same as 2512 to D2513
D2653
DNR_L1_8
SP ramp-down rate of group 8
D2654 to D2700