![YOKOGAWA UTAdvanced Series User Manual Download Page 204](http://html1.mh-extra.com/html/yokogawa/utadvanced-series/utadvanced-series_user-manual_3541677204.webp)
6-103
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Description
Range and meaning of value
D5942
SP.B0
Bit-0 of SP number
Set an I relay number of contact input.
0: OFF (Disable)
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area *
DI21: 5057, DI22: 5058, DI23: 5059,
DI24: 5060, DI25: 5061, DI26: 5062 *
E3-terminal area
DI31: 5073, DI32: 5074, DI33: 5075,
DI34: 5076, DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093, DI46: 5094 *
*: [DI26: 5062] and [DI46: 5094] are only for UT55A
and UP55A.
D5943
SP.B1
Bit-1 of SP number
D5944
SP.B2
Bit-2 of SP number
D5945
SP.B3
Bit-3 of SP number
D5946
D5947
PN.BC
Bit changing method of PID number
Same as D5941
D5948
PN.B0
Bit-0 of PID number
Same as D5942
D5949
PN.B1
Bit-1 of PID number
D5950
PN.B2
Bit-2 of PID number
D5951
PN.B3
Bit-3 of PID number
D5953
PT.BC-D
*1
Bit changing method of program pattern
number
Same as D5941
D5954
PT.B0-D
*1
Bit-0 of program pattern number
Same as D5942
D5955
PT.B1-D
*1
Bit-1 of program pattern number
D5956
PT.B2-D
*1
Bit-2 of program pattern number
D5957
PT.B3-D
*1
Bit-3 of program pattern number
D5958
PT.B4-D
*1
Bit-4 of program pattern number
D5959
PT.B5-D
*1
Bit-5 of program pattern number
D5960
MP.BC_L1
Bit changing method of manual preset
output number
Same as D5941
D5961
MP.B0_L1
Bit-0 of manual preset output number
Same as D5942
D5962
MP.B1_L1
Bit-1 of manual preset output number
D5963
MP.B2_L1
Bit-2 of manual preset output number
D5964
D5965
MP.BC_L2
Bit changing method of manual preset
output number
Same as D5941
D5966
MP.B0_L2
Bit-0 of manual preset output number
Same as D5942
D5967
MP.B1_L2
Bit-1 of manual preset output number
D5968
MP.B2_L2
Bit-2 of manual preset output number
D5969 to D6000
D6001
MSG1
Messege-1 *2
20-digit value of alphanumeric characters can be
set.
Arrangement:
D6001, D6002, D6003, D6004, D6005, D6006,
D6007, DD6008, D6009, D6010, D6011
Write “0x00” to the register after the character
string.
D6002
MSG1
D6003
MSG1
D6004
MSG1
D6005
MSG1
D6006
MSG1
D6007
MSG1
D6008
MSG1
D6009
MSG1
D6010
MSG1
D6011
MSG1
D6012 to D6020
*2: With regards to the information on D6001 to D6011, D6021 to D6031, D6041 to D6051, and
D6061 to D6071, 11 D registers comprise one message.
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...