14.4 UT75A D Registers
For Input Ladder Calculation (D7001 to D7100)
D7001 to D7010
Register
No.
Description
Range and meaning of value
D7001
X_PV
PV analog input
-5.0 to 105.0%
D7002
X_PV2
PV2 analog input
-5.0 to 105.0%
D7003
X_AIN2
AIN2 aux. analog input
-5.0 to 105.0%
D7004
D7005
X_AIN4
AIN4 aux. analog input
-5.0 to 105.0%
D7006 to D7010
Bit Configuration of D7011:
X000
(DI1-DI3 status: equipped as standard)
Bit
Symbol
Event
0
X_DI1
DI1 status
(0: OFF 1: ON)
1
X_DI2
DI2 status
(0: OFF 1: ON)
2
X_DI3
DI3 status
(0: OFF 1: ON)
3 to 15
Bit Configuration of 7014:
X300_E3
(DI31-DI35 status: E3-terminal area)
Bit
Symbol
Event
0
X_DI31
DI31 status
(0: OFF 1: ON)
1
X_DI32
DI32 status
(0: OFF 1: ON)
2
X_DI33
DI33 status
(0: OFF 1: ON)
3
X_DI34
DI34 status
(0: OFF 1: ON)
4
X_DI35
DI35 status
(0: OFF 1: ON)
5 to 15
Bit Configuration of D7015:
X400_E4
(DI41-DI46 status: E4-terminal area)
Bit
Symbol
Event
0
X_DI41
DI41 status
(0: OFF 1: ON)
1
X_DI42
DI42 status
(0: OFF 1: ON)
2
X_DI43
DI43 status
(0: OFF 1: ON)
3
X_DI44
DI44 status
(0: OFF 1: ON)
4
X_DI45
DI45 status
(0: OFF 1: ON)
5
X_DI46
DI46 status
(0: OFF 1: ON)
6 to 15
D7051 to D7100
Register
No.
Description
Range and meaning of value
D7051
PVIN_CTL
Control PV input
-
5.0 to 105.0% of PV input range (EU)
D7052
PVIN1_CTL
Control PV input 1
D7053
PVIN2_CTL
Control PV input 2
D7054
PVIN3_CTL
Control PV input 3
D7055
PVIN4_CTL
Control PV input 4
D7056
RSP_CTL
Control RSP input
0.0 to 100.0% of RSP input range (EU)
D7057
TRK_CTL
Control tracking input
-5.0 to 105.0% of TRK input range (EU)
D7058
FF_CTL
Control feedforward input
-100.0 to 100.0% of FF input range (EU)
D7059 to D7060
D7061
PV2IN_CTL
Control PV2 input
-5.0 to 105.0% of PV input range (EU)
D7062 to D7065
D7066
RSP2_CTL
Control RSP2 input
0.0 to 100.0% of RSP input range (EU)
D7067
TRK2_CTL
Control tracking input 2
-5.0 to 105.0% of TRK input range (EU)
D7068 to D7100
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...