14-33
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Loop-1 SP-related Setting (D2701 to D2800)
Register
No.
Description
Range and meaning of value
D2701
RMS_L1
Remote input method
0: RSP (Via remote (aux. analog) input)
1: COM (Via communication)
RSP is not displayed if the remote (auxiliary analog)
input is not specified.
COM is not displayed if the communication function
is not specified.
When neither the remote (auxiliary analog) input
nor communication function is specified, this
parameter is not displayed.
D2702
RFL_L1
Remote input filter
0: OFF (Disable)
1 to 120 s
D2703
RT_L1
Remote input ratio
SP = Remote input x RT + Remote input bias
0.001 to 9.999
D2704
RBS_L1
Remote input bias
-100.0 to 100.0% of PV input range span (EUS)
D2705 to D2706
D2707
TMU_L1
SP ramp-rate time unit
0: HOUR (Ramp-up rate or ramp-down rate per
hour)
1: MIN (Ramp-up rate or ramp-down rate per
minute)
D2708 to D2709
D2710
SPT_L1
SP tracking selection
Tracking is performed when the mode changes
from Remote to Local. (The local setpoint keeps
track of the remote setpoint.)
0: OFF (Disable)
1: ON (Enable)
D2711
PVT_L1
PV tracking selection
Causes the setpoint to keep track of the PV so the
setpoint automatically reverts to its original value at
a preset rate of change. The UPR, DNR, and TMU
are used in combination.
Operating conditions:
1
) MAN → AUTO, 2) STOP → AUTO,
3) Power-on, 4) SP number change,
5) SP change
0: OFF (Disable)
1: ON (Enable)
D2712 to D2800