![YOKOGAWA UTAdvanced Series User Manual Download Page 749](http://html1.mh-extra.com/html/yokogawa/utadvanced-series/utadvanced-series_user-manual_3541677749.webp)
14-92
IM 05P07A01-01EN
14.4 UT75A D Registers
Register
No.
Description
Range and meaning of value
D5723
EV1_L1
L
oop-1 EV1 display condition registration
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4326: Link to alarm 5 (Lit when the alarm occurs)
4327: Link to alarm 6 (Lit when the alarm occurs)
4329: Link to alarm 7 (Lit when the alarm occurs)
4330: Link to alarm 8 (Lit when the alarm occurs)
4337: Link to Loop-2 alarm 1 (Lit when the alarm occurs)
4338: Link to Loop-2 alarm 2 (Lit when the alarm occurs)
4339: Link to Loop-2 alarm 3 (Lit when the alarm occurs)
4341: Link to Loop-2 alarm 4 (Lit when the alarm occurs)
4342: Link to Loop-2 alarm 5 (Lit when the alarm occurs)
4343: Link to Loop-2 alarm 6 (Lit when the alarm occurs)
4345: Link to Loop-2 alarm 7 (Lit when the alarm occurs)
4346: Link to Loop-2 alarm 8 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm occurs)
4530: Heater break alarm 2 (Lit when the alarm occurs)
5025 to 5027: Link to DI1-DI3 (Lit when the contact is closed)**
5073 to 5077: Link to DI31-DI35 (E3-terminal area) (Lit
when the contact is closed)**
5089 to 5094: Link to DI41-DI46 (E4-terminal area) (Lit
when the contact is closed)**
5153 to 5155: Link to AL1-AL3 (Lit when the contact is closed)**
5185 to 5189: Link to DO21-DO25 (E2-terminal area) (Lit
when the contact is closed)**
**: Initial value. The contact action changes by the
setting of each "contact type" parameter.
For other functions, see the Chapter 15 Functions and
Applications of I Relays (for UT75A).
D5724
EV2_L1
L
oop-1 EV2 display condition registration
D5725
EV3_L1
L
oop-1 EV3 display condition registration
D5726
EV4_L1
L
oop-1 EV4 display condition registration
D5727
EV5_L1
L
oop-1 EV5 display condition registration
D5728
EV6_L1
L
oop-1 EV6 display condition registration
D5729
EV7_L1
L
oop-1 EV7 display condition registration
D5730
EV8_L1
L
oop-1 EV8 display condition registration
D5731
EV1_L2
L
oop-2 EV1 display condition registration
D5732
EV2_L2
L
oop-2 EV2 display condition registration
D5733
EV3_L2
L
oop-2 EV3 display condition registration
D5734
EV4_L2
L
oop-2 EV4 display condition registration
D5735
EV5_L2
L
oop-2 EV5 display condition registration
D5736
EV6_L2
L
oop-2 EV6 display condition registration
D5737
EV7_L2
L
oop-2 EV7 display condition registration
D5738
EV8_L2
L
oop-2 EV8 display condition registration