![YOKOGAWA UTAdvanced Series User Manual Download Page 188](http://html1.mh-extra.com/html/yokogawa/utadvanced-series/utadvanced-series_user-manual_3541677188.webp)
6-87
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Register
No.
Description
Range and meaning of value
D5181
IN_E4
AIN4 aux. analog input type
Same as D5121
D5182
UNIT_E4
AIN4 aux. analog input unit
Same as D5102
D5183
DP_E4
Maximum value of AIN4 aux. analog input
position
Same as D5103
D5184
RH_E4
Maximum value of AIN4 aux. analog input range
Same as D5144, D5145
D5185
RL_E4
Minimum value of AIN4 aux. analog input range
D5186
SDP_E4
AIN4 aux. analog input scale decimal point
position
Same as D5103
D5187
SH_E4
Maximum value of AIN4 aux. analog input scale
Same as D5107, D5108
D5188
SL_E4
Minimum value of AIN4 aux. analog input scale
D5189
BSL_E4
AIN4 aux. analog input burnout action
Same as D5109
D5190 to D5191
D5192
A.BS_E4
AIN4 aux. analog input bias
-100.0 to 100.0% of AIN4 input range span (EUS)
D5193
A.FL_E4
AIN4 aux. analog input filter
Same as D5113
D5194
A.SR_E4
AIN4 aux. analog input square root
extraction
Same as D5114
D5195
A.LC_E4
A
IN4 aux. analog input low signal cutoff
Same as D5115
D5196
D5197
DI6.D_E4
DI46 contact type
Same as D5137
D5198 to D5200
D5201
P.UNI_L1
L
oop-1 control PV input unit
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
D5202
P.DP_L1
Loop-1 control PV input decimal point
position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
D5203
P.RH_L1
L
oop-1 maximum value of control PV input range
-
19999 to 30000, (P.RL<P.RH), | P.RH - P.RL | ≤ 30000
D5204
P.RL_L1
L
oop-1 minimum value of control PV input range
D5205
PV.HL
Input switching PV high limit (in Loop
control with PV switching)
0
.0 to 100.0% of control PV input range (EU), (PV.HL>PV.
LL)
D5206
PV.LL
Input switching PV low limit (in Loop
control with PV switching)
D5207
PV.2C
Input switching action (in Loop control
with PV switching)
0: Switch based on low limit of temperature range
1: Switch using the parameter PV.HL
2: Switch using DI
3: Switch based on high limit of temperature range
D5208
PV.AS
Input computation selection (in Loop
control with PV auto-selector)
0: Max. value
1: Min. value
2: Ave. value
3: Input 1 - Input 2
4: Input 2 - Input 1
D5209
PV.NU
Number of inputs (in Loop control with
PV auto-selector)
2: Use Input 1 and Input 2
3: Use Input 1, Input 2, and Input 3
4: Use 4 inputs
D5210
SPH_L1
Loop-1 SP high limit
0
.0 to 100.0% of PV input range (EU), (SPL<SPH)
D5211
SPL_L1
Loop-1 SP low limit
D5210 to D5220
D5221
P.UNI_L2
L
oop-2 control PV input unit (in Cascade control)
Same as D5201
D5222
P.DP_L2
L
oop-2 control PV input decimal point
position (in Cascade control)
Same as D5202
D5223
P.RH_L2
Loop-2 maximum value of Control PV
input range (in Cascade control)
Same as D5203, D5204
D5224
P.RL_L2
Loop-2 minimum value of Control PV
input range (in Cascade control)
D5225 to D5229
D5230
SPH_L2
Loop-2 SP high limit
Same as D5210, D5211
D5231
SPL_L2
loop-2 SP low limit
D5225 to D5300