6.6 GREEN Series Compatible D Registers
D0231: A1_G (Alarm-1 setpoint for GREEN Series) (For UT400 Series)
Register
No.
Symbol
Event
GREEN Series UTAdvanced
D0231
A1
A1_G
-19999 to 30000 (Set a value within the input range.)
Write: The value written in A1_G will be written in the register of A1_L1_1 to A1_L1_4.
A1_L1_1 (D2504)
A1_L1_2 (D2524)
A1_L1_3 (D2544
)
A1_L1_4 (D2564)
Note
: When the same value as the current value is written to A1_G, the action to write
A1_L1_1 through A1_L1_4 is performed again. At this time, if different values are set in
A1_L1_1 through A1_L1_4, they are overwritten by the same value.
Read: The alarm-1 setpoint of the group number being selected in CSPNO.(D0210).
D0232: A2_G (Alarm-2 setpoint for GREEN Series) (For UT400 Series)
Register
No.
Symbol
Event
GREEN Series UTAdvanced
D0232
A2
A2_G
-19999 to 30000 (Set a value within the input range.)
Write: The value written in A2_G will be written in the register of A2_L1_1 to A2_L1_4.
A2_L1_1 (D2505)
A2_L1_2 (D2525)
A2_L1_3 (D2545
)
A2_L1_4 (D2565)
Note
: When the same value as the current value is written to A2_G, the action to write
A2_L1_1 through A2_L1_4 is performed again. At this time, if different values are set in
A2_L1_1 through A2_L1_4 , they are overwritten by the same value.
Read: The alarm-2 setpoint of the group number being selected in CSPNO.(D0210).
D0233: A3_G (Alarm-3 setpoint for GREEN Series) (For UT400 Series)
Register
No.
Symbol
Event
GREEN Series UTAdvanced
D0233
A3
A3_G
-19999 to 30000 (Set a value within the input range.)
Write: The value written in A3_G will be written in the register of A3_L1_1 to A3_L1_4.
A3_L1_1 (D2506)
A3_L1_2 (D2526)
A3_L1_3 (D2546
)
A3_L1_4 (D2566)
Note
: When the same value as the current value is written to A3_G, the action to write
A3_L1_1 through A3_L1_4 is performed again. At this time, if different values are set in
A3_L1_1 through A3_L1_4 , they are overwritten by the same value.
Read: The alarm-3 setpoint of the group number being selected in CSPNO.(D0210).
D0234: A4_G (Alarm-4 setpoint for GREEN Series) (For UT400 Series)
Register
No.
Symbol
Event
GREEN Series UTAdvanced
D0234
A4
A4_G
-19999 to 30000 (Set a value within the input range.)
Write: The value written in A4_G will be written in the register of A4_L1_1 to A4_L1_4.
A4_L1_1 (D2507)
A4_L1_2 (D2527)
A4_L1_3 (D2547
)
A4_L1_4 (D2567)
Note
: When the same value as the current value is written to A4_G, the action to write
A4_L1_1 through A4_L1_4 is performed again. At this time, if different values are set in
A4_L1_1 through A4_L1_4 , they are overwritten by the same value.
Read: The alarm-4 setpoint of the group number being selected in CSPNO.(D0210).