14-57
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT75A)
14
14.4 UT75A D Registers
Loop-2 Control Action-related Setting (D4601 to D4690)
Register
No.
Description
Range and meaning of value
D4601
SC_L2
Super function
0: OFF (Disable)
1: Overshoot suppressing function (normal mode)
2: Hunting suppressing function (stable mode)
Enables to answer the wider characteristic
changes compared with response mode.
3: Hunting suppressing function (response mode)
Enables quick follow-up and short converging
time of PV for the changed SP.
4: Overshoot suppressing function (strong
suppressing mode)
Note: Setpoints 2 and 3 must be used in PID control
or PI control. Disabled in the following controls:
1) ON/OFF control, 2) PD control, 3) P control,
4) Heating/cooling control
Do not use the function for the control
processes with response such as flow or
pressure control.
D4602
D4603
AT.TY_L2
Auto-tuning type
0: Normal, 1: Stability
D4604
AT.OH_L2
Output high limit in auto-tuning
-5.0 to 105.0% (Disabled in Heating/cooling control)
D4605
AT.OL_L2
Output low limit in auto-tuning
D4606
AT.BS_L2
SP bias in auto-tuning
-100.0 to 100.0% of PV input range span (EUS)
D4607 to D4612
D4613
GW_L2
Non-linear control gap width
0: OFF
0.0+1digit to 50.0% of PV input range span (EUS)
D4614
GG_L2
Non-linear control gain
0.001 to 1.000
D4615 to D4625
D4626
AR_L2
Anti-reset windup (excess integration prevention) 0: AUTO, 50.0 to 200.0%
D4627
D4628
OLMT_L2
Output limiter switch
0: OFF (Disable output limiter in MAN mode)
1: ON (Enable output limiter in MAN mode)
D4629
O
PR.U_L2
Upper-side output velocity limiter
0: OFF (Disable), 0.1 to 100.0%/s
D4630
O
PR.L_L2
Lower-side output velocity limiter
D4631
MPON_L2
Manual preset output number selection
Select the output used in MAN mode when
switched from AUTO to MAN mode.
0: OFF (Hold the control output in AUTO mode
(bumpless))
1: Use manual preset output 1 (output bump)
2: Use manual preset output 2 (output bump)
3: Use manual preset output 3 (output bump)
4: Use manual preset output 4 (output bump)
5: Use manual preset output 5 (output bump)
D4632
MPO1_L2
Manual preset output 1
-5.0 to 105.0%
D4633
MPO2_L2
Manual preset output 2
D4634
MPO3_L2
Manual preset output 3
D4635
MPO4_L2
Manual preset output 4
D4636
MPO5_L2
Manual preset output 5
D4637 to D4652
D4653
RP1_L2
Reference point 1
0.0 to 100.0% of PV input range (EU)
(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5 ≤ RP6 ≤ RP7)
D4654
RP2_L2
Reference point 2
D4655
RP3_L2
Reference point 3
D4656
RP4_L2
Reference point 4
D4657
RP5_L2
Reference point 5
D4658
RP6_L2
Reference point 6
D4659
RP7_L2
Reference point 7
D4660
RHY_L2
Zone PID switching hysteresis
0.0 to 10.0% of PV input range span (EUS)
D4661
RDV_L2
Reference deviation
0: OFF (Disable)
0.0 + 1 digit to 100.0% of PV input range span (EUS)
D4662 to D4690