6-43
IM 05P07A01-01EN
Functions and
Applications of D Registers (for UT55A/UT52A/UP55A)
6
6.4 UT55A/UT52A/UP55A D Registers
Loop-1 Control Action-related Setting (D3501 to D3600)
Register
No.
Description
Range and meaning of value
D3501
SC_L1
Super function
0: OFF (Disable)
1: Overshoot suppressing function (normal mode)
2: Hunting suppressing function (stable mode)
Enables to answer the wider characteristic
changes compared with response mode.
3: Hunting suppressing function (response mode)
Enables quick follow-up and short converging
time of PV for the changed SP.
4: Overshoot suppressing function (strong
suppressing mode)
Note: Setpoints 2 and 3 must be used in PID control
or PI control. Disabled in the following controls:
1) ON/OFF control, 2) PD control, 3) P control,
4) Heating/cooling control
Do not use the function for the control
processes with response such as flow or
pressure control.
D3502
D3503
AT.TY_L1
Auto-tuning type
0: Normal
1: Stability
D3504
AT.OH_L1
Output high limit in auto-tuning
-5.0 to 105.0% (Disabled in Heating/cooling control)
D3505
AT.OL_L1
Output low limit in auto-tuning
D3506
AT.BS_L1
SP bias in auto-tuning
-100.0 to 100.0% of PV input range span (EUS)
D3507 to D3510
D3511
STM
Sample PI sampled time
0 to 9999 s
D3512
SWD
Sample PI control time span
0 to 9999 s
D3513
GW_L1
Non-linear control gap width
0: OFF
0.0+1digit to 50.0% of PV input range span (EUS)
D3514
GG_L1
Non-linear control gain
0.001 to 1.000
D3515 to D3516
D3517
BD
Batch PID deviation setpoint
0
.0 to 100.0% of PV input range span (EUS)
D3518
BB
Batch PID bias
0.0 to 100.0%
D3519
BL
Batch PID lock-up width
0
.0 to 100.0% of PV input range span (EUS)
D3520
D3521
FLG
F
eedforward first-order lag time constant
0: OFF, 1 to 120 s
D3522
FGN
Feedforward gain
-9.999 to 9.999
D3523
FBI
Feedforward input bias
-100.0 to 100.0%
D3524
FBO
Feedforward output bias
-999.9 to 999.9%
D3525
D3526
A
R_L1
Anti-reset windup (excess integration prevention) 0: AUTO, 50.0 to 200.0%
D3527
O
PR_L1
Output velocity limiter
0: OFF (Disable), 0.1 to 100.0%/s
D3528
O
LMT_L1
Output limiter switch
0: OFF (Disable output limiter in MAN mode)
1: ON (Enable output limiter in MAN mode)
D3529 to D3530
D3531
MPON_L1
Manual preset output number selection
Select the output used in MAN mode when
switched from AUTO to MAN mode.
0: OFF (Hold the control output in AUTO mode
(bumpless))
1: Use manual preset output 1 (output bump)
2: Use manual preset output 2 (output bump)
3: Use manual preset output 3 (output bump)
4: Use manual preset output 4 (output bump)
5: Use manual preset output 5 (output bump)
D3532
MPO1_L1
Manual preset output 1
-5.0 to 105.0%
However, output is limited to the output high limit
and low limit.
D3533
MPO2_L1
Manual preset output 2
D3534
MPO3_L1
Manual preset output 3
D3535
MPO4_L1
Manual preset output 4
D3536
MPO5_L1
Manual preset output 5
D3537 to D3550
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...