14-80
IM 05P07A01-01EN
14.4 UT75A D Registers
Input Setting (D5101 to D5300)
Register
No.
Description
Range and meaning of value
D5101
IN
PV input type
0: OFF (Disable)
1: K1 (-270.0 to 1370.0°
C
/ -450.0 to 2500.0 F)
2: K2 (-270.0 to 1000.0°C / -450.0 to 2300.0 F)
3: K3 (-200.0 to 500.0°C / -200.0 to 1000.0 F)
4: J (-200.0 to 1200.0°C / -300.0 to 2300.0 F)
5: T1 (-270.0 to 400.0°C / -450.0 to 750.0 F)
6: T2 (0.0 to 400.0°C / -200.0 to 750.0 F)
7: B (0.0 to 1800.0°C / 32 to 3300 F)
8: S (0.0 to 1700.0°C / 32 to 3100 F)
9: R (0.0 to 1700.0°C / 32 to 3100 F)
10: N (-200.0 to 1300.0°C / -300.0 to 2400.0 F)
11: E (-270.0 to 1000.0°C / -450.0 to 1800.0 F)
12: L (-200.0 to 900.0°C / -300.0 to 1600.0 F)
13: U1 (-200.0 to 400.0°C / -300.0 to 750.0 F)
14: U2 (0.0 to 400.0°C / -200.0 to 1000.0 F)
15: W (0.0 to 2300.0°C / 32 to 4200 F)
16: PL2 (0.0 to 1390.0°C / 32.0 to 2500.0 F)
17: P2040 (0.0 to 1900.0°C / 32 to 3400 F)
18: WRE (0.0 to 2000.0°C / 32 to 3600 F)
30: JPT1 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
31: JPT2 (-150.00 to 150.00°C / -200.0 to 300.0 F)
35: PT1 (-200.0 to 850.0°C / -300.0 to 1560.0 F)
36: PT2 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
37: PT3 (-150.00 to 150.00°C / -200.0 to 300.0 F)
40: 0.4-2V (0.400 to 2.000 V)
41: 1-5V (1.000 to 5.000 V)
42: 4-20 (4.00 to 20.00 mA)
50: 0-2V (0.000 to 2.000 V)
51: 0-10V (0.00 to 10.00 V)
52: 0-20 (0.00 to 20.00 mA)
55: -1020 (-10.00 to 20.00 mV)
56: 0-100 (0.0 to 100.0 mV)
*W: W-5% Re/W-26% Re(Hoskins Mfg. Co.), ASTM E988
WRE: W97Re3-W75Re25
D5102
UNIT
PV input unit
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
D5103
DP
PV input decimal point position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
D5104
RH
M
aximum value of PV input range
Depends on the input type.
- For temperature input -
Set the temperature range that is actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current signal that is applied.
The scale across which the voltage / current signal is actually
controlled should be set using the maximum value of input
scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
D5105
RL
Minimum value of PV input range
D5106
S
DP
P
V input scale decimal point position
Same as D5103
D5107
SH
Maximum value of PV input scale
-
19999 to 30000, (SL<SH), | SH - SL | ≤ 30000
D5108
SL
Minimum value of PV input scale
D5109
BSL
PV input burnout action
0: OFF (Disable)
1: UP (Upscale)
2: DOWN (Downscale)
D5110
RJC
PV input reference junction
compensation
0: OFF (RJC OFF)
1: ON (RJC ON)
D5111
ERJC
PV input external RJC setpoint
-10.0 to 60.0°
C
D5112
A.BS
PV analog input bias
-
100.0 to 100.0% of PV input range span (EUS)
D5113
A.FL
PV analog input filter
0: OFF
1 to 120 s
D5114
A.SR
PV analog input square root
extraction
0: OFF (No square root extraction.)
1: Compute the square root. (The slope equals “1.”)
2: Compute the square root. (The slope equals “0.”)
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...